This trunking size calculator works to BS 7671 and the On-Site Guide Appendix E.
Trunking Size Calculator
version 1.4.2Size a cable trunking for the cables it must hold: singles by the On-Site Guide Table E5/E6 factors, sheathed and multicore cables by the 45% space-factor method. Print the record that proves it.
How this works
- Add a trunking section. A section is one trunking size on one route: set its material, size (or Auto), orientation and compartments, then drop cables in, or pick a typical situation and edit it.
- The method follows the cable type. Single-core non-sheathed cables (BS 6004 PVC / BS 7211 LSZH) use the exact On-Site Guide Table E5 factors against the Table E6 trunking factors, extended to 240 mm² by the ESC tables. Sheathed and multicore cables use the 45% space-factor rule, with flat twin-and-earth taken as a circle of diameter equal to its MAJOR axis, as the Guide states. Both include your spare-capacity margin.
- Read the verdicts and print the record: trunking size per section, the factor or space-factor calculation, the segregation and compartment checks (fire alarm gets a partitioned compartment of its own), the grouping consequence an internal barrier does NOT remove, and the drawings.
Free to run for everyone. Engineering Toolkit subscribers get the compliance record with verbatim clause citations, the in-trunking rating check, editable Excel / Word / CSV / Text exports and My Projects.
How this size was reached
In-trunking current rating: the grouping consequence
Compliance record: the clauses, quoted verbatim
Design notes
- 1,538scenarios enumerated in each tier on 1.4.2, recomputed from the source tables
- 37 of 37steel factors verified against Table E6
- 1.5 to 240 mm2single-core range sized by the factor method
- 0findings on the 1.4.2 re-run, both tiers
- Last reviewed
- September 2026
- Data basis
Show the full record
IET On-Site Guide Appendix E (Tables E5/E6, the 45% space factor rule with the major-axis definition); ESC Technical Manual T113-1 and T113-3 (cable factors extended to 240 mm2, spare capacity rule, internal areas); BS 7671 (521.5.1, 521.7, 521.10.1, 521.10.202, 527.2.2, 528.1, Appendix 4 Reference Method B and Table 4C1); BS 5839-1:2025 35.5, BS 5266-1:2025 8.2.6, BS 8519 cl.15/16 and Annex B; Legrand Salamandre 2019 standard range; MK PVCu 45% areas; BS 7629-1 and Prysmian FP200 Gold dimensions; OSG Table D4 supports; Quelfire tested firestop details.
- Validated against
Show the full record
26/09/2026 (1.4.2): the printed report, which is part of the Engineering Toolkit, had shown no sizing steps, and none of the check lines marked NOTE, since 1.3.2, released on 4 September 2026. In 1.3.2 the report section with the sizing steps was renamed "How this size was reached", and the printed report was not changed to match, so the SIZING BASIS heading was printed with nothing under it. The calculations, the wording shown in the tool, the Excel, Word, CSV and Text exports and the report emailed to free users were never affected by this fault. Each section of the printed report is now found by a fixed internal name rather than by its heading, and the sizing steps and those check lines are printed again. A long page of the printed report is no longer shrunk to fit one sheet: what does not fit on one sheet continues on the next, so a printed report can run to more pages than before. The text in the printed tables is now 9.5 px; in 1.4.1 it was 9 px, which printed at 6.75 pt, or smaller on a long page. Every result line, check line and sizing step now prints at 7 pt or more. The following now read should, the verb of the clause they cite: the check line, the design note and the help on intermediate cable supports in a vertical run over 5 m (ESC S309-1); the check line, the help and the design note on the offset of two cable diameters in a riser with straight runs over 32 m (BS 8519:2020 15 i); the two help lines, the warning and the check line on the fire alarm compartment (BS 5839-1:2025 35.5), and the line on the fire alarm cable colour (BS 5839-1:2025 25.9); the help and the check line on the partition for emergency lighting fed from a central power supply system (BS 5266-1:2025 8.2.6); and the design note on trunking bends (On-Site Guide Appendix E). The help on the Serves field now reads "The segregation checks depend on it", not "This drives the segregation checks". Where a line on BS 7671 Regulations 521.5.1, 521.10.1, 521.10.202, 526.8 or 527.2.2 said must or must never, it now reads shall or shall not, as in the regulation. Two statements now use must, as the On-Site Guide does: on lighting suspension trunking, where the tabulated support spacings do not apply, the manufacturer's instructions must be followed (Table D4 note 2); and thermosetting cables that share trunking with thermoplastic (PVC) cables must be rated as thermoplastic (Appendix E). In the How this works list, flat twin-and-earth is now "taken as a circle of diameter equal to its MAJOR axis, as the Guide states", not "counted on its MAJOR axis as the Guide requires". The rating line that names a cable's own BS 7671 Appendix 4 table now cites Regulations 523.1 and 523.2, and states that the current-carrying capacity shall be selected from that table for Reference Method B, with the Table 4C1 factor, or determined in accordance with Regulation 523.3, which the line had not mentioned. The factor of 0.5 on the free-air current rating inside a fire-rated protective enclosure is now cited to BS 8519:2020 clause 6.2 NOTE 2, which states that, for cables in an enclosure of passive fire protection material, this factor may be used unless the manufacturer of the protective system advises a different one. The lines that stated the factor had given it without that condition, and six lines had cited Annex B as its source; Annex B is the worked example (390 A in free air becomes 195 A). The value 0.5 is unchanged. Each changed verb and citation was checked against the text of the clause. Where the printed report, the exports or the report emailed to free users include a reworded line, it is reworded there too. The tool name in the dark bar, Trunking Size Calculator, is now the main heading of the page; it looks the same and its words are unchanged. The green for a pass, the amber for a point to check or a warning, and the grey for a neutral mark are now darker, so that any white text on them meets the 4.5:1 contrast that the Web Content Accessibility Guidelines 2.2 require at level AA for text of 12 px; this change applies only to the colours, not to any calculation, result, wording or layout. Amber text on a light background is also a darker amber, with a contrast of at least 4.5:1. The Cross-section and Run detail drawings, in the tool and in the printed report, and the cross-section drawing in the exports are now drawn in the darker green and amber. The panel for saving and exporting, below the results, keeps its present colours for now. Apart from these changes, the calculations and every size, factor, limit and result are unchanged, and so are the text, dimensions and values in the drawings. The 1,538 scenarios in each tier, the derived-input check, the term-of-art check, the length and storey height checks added in 1.3.3 and 1.3.4, and the two citation checks for BS 5839-1:2025 and BS 5266-1:2025 were re-run on 1.4.2 with no findings. The automated check that reads every line that can be shown in the tool now also includes each change in this release. In a new automated check, a set of cases is printed and compared with the tool: every result line, check line and sizing step shown in the tool is in the printed report at 7 pt or more, and the check fails on a copy with the 1.3.2 fault put back. The automated check of how the tool looks now also includes the colours and the main heading. All three pass on 1.4.2 and fail on 1.4.1; verified live after upload. 26/09/2026 (1.4.1): the rule that allows two or more circuits in the same trunking system is now cited to BS 7671 Regulation 521.6 rather than 521.7, which is the rule for two or more circuits in one multicore cable. The correction is in the Design notes, the subscriber compliance record, the list of the compliance record's clauses shown to free users and the References line in the printed report, the exports and the report emailed to free users; the quoted regulation text was already correct. The note on steel trunking as the protective conductor now cites Regulation 543.2.5 rather than 543.2.2, which is about the enclosure or frame of switchgear, controlgear or a busbar trunking system. The sources listed after the rating table now cite Installation Methods 6 to 9 of Table 4A2 rather than 6 and 7 only; 8 and 9 are multicore cable in trunking on a wall. The three corrected BS 7671 citations were checked against the text of BS 7671:2018+A4:2026. Two fire alarm lines were corrected against BS 5839-1:2025 35.5: the help on each cable's "In" field (the compartment the cable runs in) reads should, not must, and the fire alarm compartment check line ends "reserved solely for the fire alarm cables". Other lines in the tool and the reports were corrected for grammar, punctuation, repeated words, missing degree signs and one idiom, and the blurred example line shown to free users now names the figure as Iz in the trunking, which is a current-carrying capacity, not a current. The Cross-section and Run detail drawings, in the tool and in the printed report, are now drawn in the font and colours of the PD Power Distribution tool, and so is the cross-section drawing in the exports. The cable service colours are a colour code and are unchanged. In the printed report, the accents, the ruled lines and the table headers, now light grey with dark text, are in the new colours. Apart from the drawings and the corrected citations and wording, the text, layout, font, font sizes and page breaks of the printed report are unchanged. The printed report for each of the eight typical situations was saved as a PDF from 1.4.0 and from 1.4.1 and compared: each 1.4.1 copy has the same number of pages as its 1.4.0 copy, and the text differs only by the corrected citations and wording. The text in the tool's fields is now 14 px; in 1.4.0 some fields were 12 or 13 px. When the page is under 768 px wide, as on a phone, the text in the tool's fields is 16 px, so a phone does not zoom the page when a field is tapped. The panel for saving and exporting, below the results, keeps its present colours for now. The calculations and every size, factor, limit and result are unchanged, and so are the text, dimensions and values in the drawings. Apart from the cross-section drawing in the exports, the exports and the report emailed to free users change only in the corrected citations and wording. The 1,538 scenarios in each tier, the derived-input check, the term-of-art check, the length and storey height checks added in 1.3.3 and 1.3.4, and the two citation checks for BS 5839-1:2025 and BS 5266-1:2025 were re-run on 1.4.1 with no findings. Every line that can be shown in the tool is now read by a new automated check, and the automated check of how the tool looks now also includes the drawings and the printed report. Both pass on 1.4.1 and fail on the 1.4.0 build; verified live after upload. 26/09/2026 (1.4.0): the tool now looks like the PD Power Distribution tool, with the same font and colours, and the same style of buttons, fields, tables, result tiles and check lines. The tool name and version are shown in a new dark bar at the top of the tool, and the Start again button was moved into that bar from beside the description; it works as before. The calculations, every result, the drawings, the wording shown in the tool (apart from the tool name and version in the dark bar), the printed report, the report emailed to free users and the exports are unchanged. The 1,538 scenarios in each tier, the derived-input check, the term-of-art check, the length and storey height checks added in 1.3.3 and 1.3.4, and the two citation checks for BS 5839-1:2025 and BS 5266-1:2025 were re-run on 1.4.0 with no findings. A new automated check of how the tool looks, run at desktop width and at a 390 px phone width, passes on 1.4.0 and fails on the 1.3.8 build; verified live after upload. 16/09/2026 (1.3.8): the wording in the tool was revised in plain UK English. The compliance record line and the How this works list now say in the tool, and the segregation and compartment checks are called checks. The calculations, the printed report and the exports are unchanged. The 1,538 scenarios in each tier, the derived-input check and the term-of-art check were re-run on 1.3.8 with no findings; verified live after upload. 15/09/2026 (1.3.7): the notes written inside the program code were rewritten in plain UK English. The calculations, the wording shown in the tool, the printed report and the exports are unchanged. The 1,538 scenarios in each tier were re-run on 1.3.7 with no findings; verified live after upload. 15/09/2026 (1.3.5 and 1.3.6): every citation of the fire alarm and emergency lighting standards was read back against the current editions. BS 5839-1:2025 replaced the 2017 edition: the compartment rule is now cited to 35.5, non-metallic trunking to BS EN 50085-1 (35.7) and the support note to 35.3, which says non-metallic trunking as the sole means of support is likely to be precluded. BS 5266-1:2025 replaced the 2016 edition: its clause 8.2 applies to emergency lighting fed from a central power supply system, so the partition, the marking of reserved trunking and the non-combustible support are now stated for that case, and supply cables to self-contained luminaires are named as installed like a normal lighting circuit (8.1); the subscriber compliance record quotes clause 8.2.6 of the 2025 edition word for word. Two new automated checks read every citation, and the wording of every program file, in the tool, the report and the printed sheet, and fail on the 1.3.4 and 1.3.5 builds; the 1,538 scenarios, the derived-input check and the term-of-art check were re-run on 1.3.6 in both tiers with no findings; no factor, size or limit changed; verified live after upload. 11/09/2026 (1.3.4): a check across every PD tool for an input shown to every user that only a minority case reads. The storey height field was shown on every vertical section, although only a vertical section that penetrates a fire-rated element reads it, for the slab crossings in the support note. It now shows only once that box is ticked on a vertical section, and ticking the box reveals it at once. An automated check for it was added and fails on the 1.3.3 build; the 1,538 scenarios, the derived-input check and the term-of-art check were re-run on 1.3.4 in both tiers with no findings; no factor, size or limit changed; verified live after upload. 10/09/2026 (1.3.3): a check across every PD tool for a figure printed as entered that the user never gave. Every new section started with a 6 m length that was printed in the check row, the schedule and the report as if entered, and a vertical section left at it was told to provide intermediate supports for a 6 m run nobody had specified. A new section now starts with the length blank: the capacity result does not depend on it, and the support count, the pin racks and the fire-stopping positions ask for it until it is entered. An automated check now tests a fresh section in both tiers (blank field, the request line, no vertical note without a length, the note once a length is entered, blank again after Start again and on an added section) and fails on the 1.3.2 build; the 1,538 scenarios, the derived-input check and the term-of-art check were re-run on 1.3.3 with no findings; no factor, size or limit changed; verified live after upload. 04/09/2026 (1.3.2): the sizing basis is now headed How this size was reached and laid out as numbered steps for each section, with the section's size and verdict at the head of its card and every figure in bold, so the calculation behind the answer reads as a worked example for the case entered. The steps are the same calculations as before and the report shows them under the same heading. The 1,538 scenarios were re-run on 1.3.2 in both tiers with no findings; no factor, size or limit changed; verified live after upload. 04/09/2026 (1.3.1): a check of whether every input the standard names by a term of art is defined in the tool, printed back and questioned where a wrong entry can be seen. The custom internal width and depth fields took the catalogue size, which names trunking by its outside dimensions, so 75 x 50 entered gave 3750 mm2 where the tool's own Table E6 figure for that size is 3456 mm2; the custom cable diameter field took the conductor size in place of the overall diameter. Both now show help naming the figure meant and the entry that is wrong. A custom steel or PVCu size equal to one on the standard list, or a diameter equal to a conductor size, prints a check line with the figure the tool holds while still giving the answer; a fire-rated system, always entered by hand, is not questioned this way. The 1,538 scenarios were re-run on 1.3.1 with no findings; no factor, size or limit changed; verified live after upload. 04/09/2026: the full input range was enumerated, 1,538 scenarios in each tier: every single-core size from 1.5 to 240 mm2 in PVC and LSZH, solid and stranded, FP200 and BS 7629 multicores, ESC three-core and flat cables, mixed sets, at four quantities, three spare capacities, one and two compartments, steel and PVCu, every standard steel size checked manually, the fire-rated path with and without the manufacturer size, and blank or nonsense spare entries. The proposed size, the verdict word, the support centres against On-Site Guide Table D4, the grouping factor against BS 7671 Table 4C1 and the Table E5 and E6 figures were each recomputed independently from the source tables and compared with what the tool prints. No difference was found. 03/09/2026 (1.3.0): a check across every PD tool that every printed value is reached through the input the standard derives it from. A fire-rated system was found to be sized and passed on the steel Table E6, with its current rating printed without the BS 8519 Annex B correction: it now asks for the manufacturer's internal size and tested support centres and prints the rating rule instead of a figure. Current ratings are given only for the FP200 cable the datasheet covers, other cables are pointed to their BS 7671 Appendix 4 table. Blank spare and blank length ask for the value; circuits beyond Table 4C1 say so; compartment widths can be entered; Band I cables state whether they are insulated for 300/500 V before the Reg 528.1 note applies; the 528.1 methods are numbered 1 to 6 as the A4 text has them. The audit checks were run in both tiers; verified live after upload; no size or factor changed on steel or PVCu. 02/09/2026 (1.2.3): every cited BS 7671 clause was read back against BS 7671:2018+A4:2026, BS 5266-1:2025 and BS 5839-1:2025; the result summary names the section with the highest utilisation and the trunking cover rule is cited to Reg 530.4.3; no size or factor changed. 02/09/2026 (1.2.2): the revised wording was checked in the tool against the house style, using the FF core transition preset; no size or factor changed. 33 checks were run: both ESC worked examples (unit system and space factor), the RM Technical chart example, a real project cable schedule, and the published internal-area figures (75x50 = 3455 mm2, 75x75 = 5270 mm2, reproduced by factor / 0.45). All 37 steel factors were verified against On-Site Guide Table E6. The grouping check was verified against the FP200 Gold datasheet and Table 4C1.
- Sizes trunking sections for single-core cables (BS 6004 PVC / BS 7211 LSZH, 1.5 to 240 mm2) by the Table E5/E6 factors and for sheathed, multicore and flat cables by the 45% space factor. Auto proposes manufacturer standard sizes; any Table E6 or custom internal size can be checked. Compartment capacity is split equally unless the compartment widths are entered: confirm real compartment areas from the catalogue. PVCu capacities are the manufacturer 45% areas; a fire-rated (BS EN 1366-5) system is sized only on the manufacturer's internal size and support centres that you enter. The grouping factor uses an estimated or user-entered circuit count up to the 20 circuits Table 4C1 tabulates. This tool checks the containment: the circuit design of record (Ib, In, Iz, voltage drop, Zs) remains the designer's; the in-trunking rating shown is the FP200 datasheet figure, other cables are pointed to their BS 7671 table.
What's changed
- September 2026 · v1.4.2The printed report lists the sizing steps and the check lines marked NOTE again; none had been printed since 1.3.2. Some check lines, notes and help now read shall, should or must, as the clause they cite does. The green, amber and grey are now darker, for a contrast above 4.5:1 with white text (Web Content Accessibility Guidelines 2.2, level AA). The calculations and results are unchanged.
- September 2026 · v1.4.1BS 7671 Regulation 521.6 is now cited for circuits sharing trunking, not 521.7, which applies to circuits sharing a multicore cable. The note on steel trunking as the protective conductor now cites Regulation 543.2.5, not 543.2.2. The drawings now use the PD Power Distribution tool font and colours, with the cable service colours kept. The calculations and results are unchanged.
- September 2026 · v1.4.0The tool now looks like the PD Power Distribution tool, with the same font and colours. The tool name and version are in a dark bar at the top, with the Start again button. The Cross-section and Run detail switch is now a row of tabs. The calculations, every result, the drawings, the printed report and the exports are unchanged.
- September 2026 · v1.3.8The wording in the tool was revised in plain UK English: the compliance record line and the How this works list now say in the tool, and the segregation and compartment checks are called checks. The calculations, the printed report and the exports are unchanged
- September 2026 · v1.3.7The notes written inside the program code were rewritten in plain UK English. The calculations, the wording shown in the tool, the printed report and the exports are unchanged
- September 2026 · v1.3.6The emergency lighting lines now cite BS 5266-1:2025: the partition in shared trunking (8.2.6), the marking of reserved trunking (8.2.5) and the non-combustible support (8.2.3) apply to luminaires fed from a central power supply system; supply cables to self-contained emergency luminaires may be installed as a normal lighting circuit (8.1). The segregation and fixing lines now read should, not must. No factor, size or limit changed.
- September 2026 · v1.3.5The fire alarm lines now cite BS 5839-1:2025, which replaced the 2017 edition: 35.5 for the compartment rule, 35.7 for non-metallic trunking to BS EN 50085-1, 25.7 for the 1 mm2 conductor minimum, 25.9 for the single cable colour and 35.3 for cable support. Two statements were corrected against the 2025 text: non-metallic trunking in a fire alarm system should conform to BS EN 50085-1, not BS 4678-4, and plastic trunking as the sole support of fire alarm cables is likely to be precluded, not precluded outright. No factor, size or limit changed.
- September 2026 · v1.3.4The storey height field shows only on a vertical section that penetrates a fire-rated element, which is the only case that reads it (the slab crossing positions in the run detail). No factor, size or limit changed
- September 2026 · v1.3.3A new section now starts with the length blank. Before, every section started at 6 m, which was printed as if it had been entered, and a vertical section left at 6 m was given a check line to provide intermediate supports. The support count, the pin racks and the fire-stopping positions are given once the length is entered. No factor, size or limit changed.
- September 2026 · v1.3.2The sizing basis is now headed How this size was reached and laid out as numbered steps for each section, with the section's size and verdict at the top of its card and every figure in bold. The steps themselves, and the report section that shows them, are the same calculations as before. No factor, size or limit changed
- September 2026 · v1.3.1The custom internal width and depth fields and the custom cable diameter field now state what to enter: the internal dimensions, not the catalogue size, and the overall diameter over the sheath, not the conductor size. Where a steel or PVCu entry equals a standard size, or an overall diameter equals a conductor size, a check line shows the figure the tool holds; the answer is still given.
- September 2026 · v1.3.0A fire-rated system is now sized on the manufacturer's internal dimensions only, with its supports at the manufacturer's tested centres. The FP200 Gold rating table now applies only to FP200 cables; for every other cable, the rating is referred to its own BS 7671 Appendix 4 table. A spare capacity or length left blank is now asked for, with no figure assumed, and a spare above 60% is refused.
- September 2026 · v1.2.3The result summary and report title name the section with the highest utilisation; the trunking cover rule is cited to BS 7671 Reg 530.4.3 rather than Section 530. No size or factor changed
- September 2026 · v1.2.2The wording was revised in plain UK English: the worst section is labelled highest utilisation, a limit is called a limit, plurals written out, the on-screen text has no dashes. No size or factor changed
- August 2026 · v1.2.1The core count numerals on the cable discs read clearly again: the white label background added in 1.2.0 no longer applies to white text on a coloured disc
- August 2026 · v1.2.0The recommended trunking sizes stay in view in a bar that follows you down the page while you edit the sections. Drawing labels have a white background so they read clearly over the cables, and a review flag on a section reads as plain text rather than a dash
- August 2026 · v1.1.0Free use is now measured in sessions: after three days of anonymous use, you enter your email address to continue free use, with no password and no account. The in-trunking rating headline (the Iz and the largest device per section) is now free in the tool. The full rating table, the circuit count basis and the verbatim compliance record stay with the Engineering Toolkit.
- August 2026 · v1.0.8Subscriber-facing copy states what the Engineering Toolkit adds rather than what the free preview lacks
- July 2026 · v1.0.7Claims audit: the Reg 527.2.3 note said every listed size exceeds 710 mm² internally, which is wrong, and is corrected (the three smallest PVCu mini-trunking sizes fall below it); the non-standard-size note now cites the 18-size Salamandre range precisely
- July 2026 · v1.0.6Vertical risers gain a storey height input (default 4 m) that places the floor slabs and their internal fire seals in the run detail. Capacity unchanged
- July 2026 · v1.0.5Run detail: the firestop support rule moved to its own line, clear of the length dimension on risers
- July 2026 · v1.0.4Identical notes raised by several sections now merge into one card, headed SECTION 1 & SECTION 2
- July 2026 · v1.0.3Auto sizing proposes manufacturer standard sizes only (Legrand Salamandre, 18 sizes), with the other Table E6 sizes still selectable; new per-section circuit count for Cg, with the counting basis stated
- July 2026 · v1.0.2Fire-rated crossings show the tested-detail support rule: independent supports both sides of every seal, the first bracket within 400 mm of each seal face, so no load transfers onto the firestop
- July 2026 · v1.0.1Run detail: the DB origin is drawn with the standard distribution board symbol
- July 2026 · v1.0.0First release: trunking sizing to BS 7671 and the On-Site Guide Appendix E. Singles by the Table E5/E6 factors to 240 mm², sheathed and multicore by the 45% space factor with the major-axis rule, plus compartment partition checks, vertical riser support, true-scale drawings and reports