On this page:

    Arc Fault Detection Devices (AFDDs) in the UK: Technical Requirements and Implementation

    Executive Summary

    Arc Fault Detection Devices (AFDDs) represent a significant advancement in electrical fire safety. This whitepaper provides a comprehensive technical analysis of AFDD requirements under BS 7671:2018+A2:2022, their operational principles, implementation challenges, and specific product solutions from leading manufacturers Hager and Schneider Electric. The document addresses the ongoing debate regarding AFDD effectiveness in ring final circuits and provides guidance for electrical professionals on risk assessment, selection, and installation.

    1. Regulatory Framework

    1.1 Evolution of AFDD Requirements in UK Standards

    The UK’s approach to Arc Fault Detection Devices is defined through the IET Wiring Regulations BS 7671:2018+A2:2022, which represents the national standard for electrical installations. The inclusion of AFDDs reflects the industry’s commitment to enhancing fire safety through technological innovation.
    Amendment 2 to the 18th Edition introduced significant changes to the recommendations for AFDD implementation. Specifically, Regulation 421.1.7 states:
    “In order to provide protection against fire, an arc fault detection device (AFDD) conforming to BS EN 62606 shall be provided for single-phase AC final circuits supplying socket-outlets with a rated current not exceeding 32 A in:
     
    (i) higher risk residential buildings
    (ii) houses of multiple occupation (HMOs)
    (iii) purpose-built student accommodation
    (iv) care homes.”
    This regulation represents a shift from the previous edition, where AFDDs were only recommended for consideration in certain locations. The current wording establishes a clearer requirement for AFDD installation in specific high-risk environments.

    1.2 Relationship with European Standards

    AFDDs in the UK must conform to BS EN 62606, which provides the product standard for these devices. This standard defines:
    • Detection requirements for both series and parallel arc faults
    • Testing methodologies to verify AFDD performance
    • Operational parameters and reliability requirements
    • Immunity to unwanted tripping
    The alignment with European standards ensures that AFDDs installed in the UK meet internationally recognized safety criteria while addressing the specific requirements of UK electrical installations.

    2. Technical Principles and Operation

    2.1 Arc Fault Detection Mechanisms

    AFDDs employ microprocessor technology to analyse electrical waveforms and identify the distinctive signatures of dangerous arcs. These devices continuously monitor the electrical circuit for the following conditions:
     
    • High-frequency noise patterns indicative of arcing
    • Current waveform distortions
    • Rapid changes in current magnitude
    • Specific frequency components associated with arc faults
    When an arc fault is detected, the AFDD automatically disconnects the circuit, preventing the arc from reaching temperatures that could ignite surrounding materials.

    2.2 Types of Arc Faults Detected

    AFDDs are designed to detect two primary types of arc faults:
     
    Series Arc Faults: These occur when current flows through an unintended break in a conductor. Common causes include damaged cables, loose connections, or broken conductor strands. Series arcs occur in line with the load and may not draw sufficient current to trigger conventional overcurrent protection.
     
    Parallel Arc Faults: These occur between live conductors (line-to-line) or between a live conductor and earth. Parallel arcs typically draw higher currents and may trigger conventional overcurrent protection if the fault current exceeds the trip threshold.

    2.3 Differentiation from Other Protective Devices

    It is essential to understand that AFDDs complement rather than replace other protective devices:
     
    • Miniature Circuit Breakers (MCBs): Provide protection against overloads and short circuits, but cannot detect low-current arcing faults.
    • Residual Current Devices (RCDs): Detect earth leakage currents but cannot identify arcing between line conductors or series arcs.
    • Residual Current Circuit Breakers with Overcurrent Protection (RCBOs): Combine RCD and MCB functions but lack specific capabilities for detecting arc faults.
    • RCBO with Arc Fault Detection (RCBO-AFDD): Integrated devices that combine overcurrent protection, residual current protection, and arc fault detection in a single module.
    AAFDDs address a protection gap in conventional systems by detecting dangerous arcing conditions that may not trigger other protective devices. When combined with RCBO functionality in a single unit (RCBO-AFDD), they offer the most comprehensive protection solution available for electrical circuits.

    3. Application Requirements in BS 7671:2018+A2:2022

    3.1 Mandatory vs. Recommended Use

    Under BS 7671:2018+A2:2022, AFDDs are required for single-phase AC final circuits supplying socket-outlets with a rated current not exceeding 32 A in specific high-risk environments. However, Regulation 421.1.7 also includes a broader recommendation to consider AFDD installation in:
     
    • Premises with sleeping accommodation
    • Locations with combustible construction materials
    • Fire propagation structures (buildings with risk of fire spread)
    • Premises with irreplaceable goods or high-value assets
     
    The regulation places responsibility on the designer to assess risk and determine whether AFDDs are necessary beyond the mandatory applications.

    3.2 Circuit Types and Ratings

    The focus on socket-outlet circuits not exceeding 32 A aligns with the typical rating used in UK domestic and commercial installations. This encompasses:
    • Standard 20 A radial circuits
    • 32 A radial circuits
    • Ring final circuits (typically protected at 32 A)
    The emphasis on these circuits reflects their prevalence in areas where people sleep and where electrical fires may pose the greatest risk to life safety.

    3.3 Installation Location Requirements

    BS 7671 specifies that AFDDs should be installed at the origin of the final circuit in a consumer unit or distribution board. This positioning ensures that the entire circuit, including the fixed wiring, is protected against arc faults.

    4. AFDD Application in Ring Final Circuits

    4.1 Technical Considerations for Ring Circuits

    The application of AFDDs on ring final circuits presents specific technical considerations. Ring circuits, which are common in UK installations, create a unique electrical environment that affects AFDD operation.
     
    According to NICEIC guidance, AFDDs are effective at detecting parallel arcing faults in ring circuits but may have limitations in detecting series arcing faults in ring configuration. This is due to the dual-path nature of ring circuits, where current can flow through either side of the ring to any connected load.

    4.2 Current Industry Guidance

    The debate regarding AFDD effectiveness on ring circuits highlights the importance of:
     
    • Continuous testing and inspection to ensure circuit integrity
    • Proper installation and maintenance of ring circuits
    • Consideration of alternative circuit designs in high-risk areas
    • Manufacturer-specific guidance for AFDD application on ring circuits
    Electrical designers should consult with AFDD manufacturers regarding the suitability of specific devices for ring circuit applications and consider the overall risk assessment when determining protection strategies.

    5. Specific AFDD Products for UK Applications

    5.1 Hager AFDD Solutions

    Hager offers a comprehensive range of AFDD solutions specifically designed for the UK market and compliant with BS 7671:2018+A2:2022 requirements. Their product lineup includes both standalone AFDD-MCB combinations and integrated RCBO-AFDD devices:

    5.1.1 Hager 20A AFDD Solutions

    ARM920U: 20A single module AFDD MCB with B curve characteristics. Key features include:
    • Single module (18mm) width for space efficiency in consumer units
    • 6kA breaking capacity to BS EN 60898
    • B curve tripping characteristics suitable for general purpose and resistive loads
    • Integrated diagnostic LED for fault indication
    • Compliance with BS EN 62606 for arc fault detection
    ARL920U: 20A single module RCBO with AFDD protection, offering comprehensive protection in a single device:
    • Combined RCBO and AFDD functionality (overcurrent, residual current, and arc fault protection)
    • 6kA breaking capacity to BS EN 60898
    • B curve tripping characteristics
    • Type A 30mA residual current protection
    • Single module (18mm) width design
    • 1m lead-free lead (LFL) for flexible installation
    • Integrated diagnostic LED for fault identification
    • Compliance with BS EN 62606 for arc fault detection

    5.1.2 Hager 32A AFDD Solutions

    Hager offers multiple 32A AFDD solutions:
    ARM932U: 32A single module AFDD MCB with B curve characteristics, featuring:
    • Single module design (18mm width)
    • 6kA breaking capacity
    • B curve tripping characteristics
    • Integrated diagnostic LED
    • BS EN 62606 compliance
    ARM982U: 32A single module AFDD MCB with C curve characteristics, offering:
    • Enhanced immunity to surge currents for motor loads and higher inrush equipment
    • 6kA breaking capacity
    • C curve tripping characteristics
    • Single module design
    • Integrated diagnostic LED
    ARL932U: 32A single module RCBO with AFDD protection, providing:
    • Integrated overcurrent, residual current, and arc fault protection
    • 6kA breaking capacity
    • B curve tripping characteristics
    • Type A 30mA residual current protection
    • Single module design
    • Diagnostic LED for fault identification
    All models provide comprehensive protection against series and parallel arc faults while maintaining compatibility with standard Hager consumer units. The RCBO-AFDD models (ARL series) offer the most complete protection solution in a space-efficient single module format.

    5.2 Schneider Electric AFDD Solutions

    Schneider Electric’s Acti9 range includes advanced AFDD solutions designed for the UK market and compliant with BS 7671:2018+A2:2022.

    5.2.1 Schneider Electric 20A AFDD Solutions

    The A9TDFD620 is Schneider’s 20A Active Arc Fault Detection RCBO, featuring:
    • Combined AFDD, MCB, and RCD functionality in a single device
    • 1P+N configuration with C curve characteristics
    • 30mA Type A-SI residual current protection
    • 10kA breaking capacity
    • All-in-one protection in a simplified and compact form
    • Diagnostic LED for easy fault identification
    • Spring terminals to reduce wiring time

    5.2.2 Schneider Electric 32A AFDDs

    The A9TDFD632 is Schneider’s 32A Active Arc Fault Detection RCBO, offering:
    • Integrated AFDD, MCB, and RCD protection
    • 1P+N configuration with C curve characteristics
    • 30mA Type A-SI residual current protection
    • 10kA breaking capacity
    • Compact design for consumer unit installation
    • Diagnostic LED system
    • Markable cable ends to facilitate installation
    Both Schneider Electric models provide comprehensive protection against electrical faults, including arc faults, overcurrents, and earth leakage in a single device.

    6. Design and Installation Considerations

    6.1 Consumer Unit Integration

    When integrating AFDDs into consumer units, designers and installers should consider:
    • Space requirements: AFDDs may require additional module space compared to standard MCBs
    • Compatibility with existing consumer unit designs
    • Heat dissipation within the enclosure
    • Accessibility for testing and maintenance
    • Clear labeling of AFDD-protected circuits
    •  
    Both Hager and Schneider Electric offer AFDD solutions designed for seamless integration with their respective consumer unit ranges.

    6.2 Coordination with Other Protective Devices

    AFDDs must be coordinated with other protective devices to ensure effective operation:
    • Selectivity with upstream protection
    • Coordination with RCDs for comprehensive fault protection
    • Integration with surge protection devices (SPDs)
    • Consideration of backup protection requirements
    Manufacturers’ technical documentation should be consulted to ensure proper coordination between protective devices.

    6.3 Testing and Verification

    BS 7671 requires that AFDDs, where installed, be recorded in the electrical installation certificate and inspected according to Part 6 of the regulations. Verification should include:
    • Functional testing using the test button
    • Visual inspection for damage or incorrect installation
    • Verification of correct rating and type
    • Documentation in installation schedules
    • Inclusion in operation and maintenance manuals
    Regular testing of AFDDs is essential to ensure continued protection against arc faults.

    7. Risk Assessment and Decision-Making

    7.1 Identifying High-Risk Applications

    Electrical designers should conduct a thorough risk assessment to identify applications where AFDDs provide significant safety benefits. Factors to consider include:
    • Presence of sleeping accommodation
    • Building construction materials and fire propagation risk
    • Value and replaceability of assets
    • Occupant vulnerability (elderly, children, disabled persons)
    • Historical data on electrical fire incidents
    • Circuit loading patterns and equipment types
    The risk assessment should be documented to support design decisions regarding AFDD implementation.

    7.2 Cost-Benefit Analysis

    While AFDDs represent an additional cost compared to standard protective devices, their benefits must be evaluated in the context of:
    • Life safety improvements
    • Property protection value
    • Insurance implications
    • Regulatory compliance
    • Reputation and liability considerations
    The relatively recent introduction of AFDDs to the UK market means they command a premium price and require additional consumer unit space. However, these factors must be balanced against the potential cost of electrical fires and the value of enhanced safety.

    7.3 Early Design Consideration

    It is imperative to identify AFDD requirements during the preliminary design stage to avoid complications later in the project. Early consideration allows for:
    • Appropriate consumer unit specification
    • Adequate space allocation
    • Proper circuit design and load distribution
    • Budget allocation for enhanced protection
    • Client education regarding AFDD benefits
    Failing to identify AFDD requirements early can lead to significant redesign costs and project delays.

    8. Practical Implementation Challenges

    8.1 Potential Arcing Causes

    Understanding the common causes of arc faults helps in designing installations that minimise risk:
    • Cable entrapment or compression during installation
    • Compromised insulation due to physical damage
    • Damage from rodents or other pests
    • Insecure connections in accessories or equipment
    • Insulation degradation due to aging or environmental factors
    Installation practices should aim to minimize these risks while AFDDs provide protection against faults that do occur.

    8.2 Unwanted Tripping Considerations

    Modern AFDDs are designed to minimize unwanted tripping, but certain loads may present challenges:
    • Brush motors with normal operational arcing
    • Certain electronic equipment with high-frequency components
    • Dimmer switches and speed controllers
    • Older appliances with less sophisticated interference suppression
    Both Hager and Schneider Electric AFDDs incorporate advanced algorithms to differentiate between dangerous arcs and normal operational arcing, reducing the likelihood of unwanted tripping.

    8.3 Retrofit Considerations

    When retrofitting AFDDs to existing installations, additional considerations include:
    • Condition assessment of existing wiring
    • Space constraints in existing consumer units
    • Potential need for consumer unit replacement
    • Circuit identification and load assessment
    • Client education regarding new protection features
    Retrofit installations may require more extensive survey and preparation work compared to new installations.

    9. Future Developments

    9.1 Evolving Standards

    The requirements for AFDDs in UK electrical installations are likely to evolve with future amendments to BS 7671. Potential developments include:
    • Expansion of mandatory applications
    • Enhanced testing requirements
    • Integration with smart building systems
    • Improved discrimination and coordination specifications
    Electrical professionals should maintain awareness of regulatory developments affecting AFDD requirements.

    9.2 Technological Advancements

    AFDD technology continues to advance, with potential future developments including:
    • Enhanced discrimination between dangerous and normal arcing
    • Reduced physical size
    • Integration with energy monitoring and management systems
    • Remote monitoring and notification capabilities
    • Improved diagnostic information
    Both Hager and Schneider Electric, and many others, continue to invest in AFDD technology development to enhance safety and functionality.

    10. TL;DR

    Arc Fault Detection Devices represent an important advancement in electrical fire safety within UK installations. Although using them in ring final circuits has some technical challenges, the safety they offer against harmful arc faults fills a major gap in traditional protection systems.
     
    BS 7671:2018+A2:2022 establishes clear requirements for AFDD installation in high-risk environments, with broader recommendations for consideration in other applications. Electrical designers and installers must understand these requirements and the technical principles of AFDD operation to implement effective protection strategies.
     
    Both Hager and Schneider Electric offer AFDD solutions specifically designed for the UK market, with models available in the critical 20A and 32A ratings required for compliance with BS 7671. These devices provide comprehensive protection against arc faults while integrating with existing Distribution Systems.
     
    Through proper risk assessment, early design consideration, and appropriate product selection, electrical professionals can enhance fire safety in UK installations and provide clients with state-of-the-art protection against arc fault hazards.

    References

    1. The Institution of Engineering and Technology. (2022). BS 7671:2018+A2:2022 Requirements for Electrical Installations. IET Wiring Regulations 18th Edition. IET.
    2. NICEIC. (2022 ). Technical Guidance on Arc Fault Detection Devices. NICEIC Group Limited.
    3. British Standards Institution. (2014). BS EN 62606:2013+A1:2017 General requirements for arc fault detection devices. BSI.
    4. Hager Ltd. (2023). Arc fault detection devices (AFDD).  
    5. Hager Ltd. (2023 ). ARM920U MCB with dangerous arc detection 1M 20A B curve 6kA. Technical Datasheet. 
    6. Hager Ltd. (2023 ). ARM932U MCB with dangerous arc detection 1M 32A B curve 6kA. Technical Datasheet
    7. Hager Ltd. (2023 ). ARM982U MCB with dangerous arc detection 1M 32A C curve 6kA. Technical Datasheet
    8. Hager Ltd. (2023 ). ARL920U RCBO with dangerous arc detection 1M 20A B 6kA A 30mA LFL 1m. Technical Datasheet.  
    9. Hager Ltd. (2023 ). ARL932U RCBO with dangerous arc detection 1M 32A B 6kA A 30mA LFL 1m. Technical Datasheet
    10. Schneider Electric UK. (2023 ). Acti9 Arc Fault Detection Devices – AFDD. 
    11. Schneider Electric UK. (2023 ). A9TDFD620 – Active arc fault detection RCBO, Acti9 iCV40H ARC, 1P + N, 20 A, C curve, 30 mA, type A-SI, 10000 A. Technical Datasheet
    12. Schneider Electric UK. (2023 ). A9TDFD632 – Active arc fault detection RCBO, Acti9 iCV40H ARC, 1P + N, 32 A, C curve, 30 mA, type A-SI, 10000 A. Technical Datasheet
    13. Professional Electrician. (2022, June 14 ). Amendment 2: Arc Fault Detection Device (AFDD) requirements. 
    14. Electrical Safety UK. (2023 ). Arc Fault Detection Devices (AFDDs). 
    15. The Institution of Engineering and Technology. (2022 ). 18th Edition changes. 
    16. BEAMA. (2022 ). What’s new for Arc Fault Detection Devices (AFDDs) in BS 7671 Amendment 2. 
    17. Electrical 4 Less. (2023 ). AFDD – Arc Fault Detection Devices. 
    18. TLC Electrical Supplies. (2023 ). AFDD Arc Fault Detection Device – Hager. 
    19. Sparks Direct. (2023 ). Hager Arc Fault Detection Device (AFDD). 
    On this page:

      Leave a Reply

      Your email address will not be published. Required fields are marked *

      share this page