PD Conduit
version 1.9.0Size a conduit for the cables in each run: polyvinyl chloride (PVC) and low smoke zero halogen (LSZH) singles by the On-Site Guide factors, FP200-type multicore by the space-factor method. Print the record of the check.
How this works
- Add a run. A run is one conduit between draw-in points. Choose the conduit material: steel, polyvinyl chloride (PVC) or pliable. Set its length and how many bends or sets it has (a double set counts as one bend), then drop cables in, or pick a typical situation and edit it.
- The sizing method depends on the cables in the run. A run of single-core non-sheathed cables only, PVC to BS 6004 or low smoke zero halogen (LSZH) to BS 7211, is sized by the On-Site Guide Appendix E unit system: the conduit factor is lower for a longer run and for more bends. As Project Design good practice, such a run that passes the Appendix E factors but fills more than 35% of the conduit reads PASS WITH WARNING, and a note gives the next size or a split across two conduits. A run with any sheathed cable (FP200-type to BS 7629-1:2015, or any LSZH sheathed cable), a mix of singles and sheathed cables, or a custom internal diameter is sized by the fallback method, the 35% space factor for conduit in Institution of Engineering and Technology (IET) Guidance Note 1, Appendix A, A5, with a geometric fit check. On a run over 3 m or with more than one bend, the working target of 30% space factor from the Project Design conduit sizing research guide is printed as a note.
- Read the verdicts and print the record: conduit size per run, the factor or space-factor calculation, the segregation checks (fire alarm cables should have a conduit of their own, BS 5839-1:2025 35.5), the enclosed current rating and the drawings.
Free to run for everyone. Engineering Toolkit subscribers get the compliance record with verbatim clause citations, the enclosed rating check, editable Excel, Word, comma-separated values (CSV) and text exports, and My Projects.
Options: conduit system
How this size was reached
Enclosed current rating: the transition consequence
Compliance record: the clauses, quoted verbatim
Design notes
- 2,190scenarios checked against independent calculations on 1.6.5, no findings
- 4 rows x 3 columnsOn-Site Guide Table D3 support spacings held in full, by conduit material
- E1 to E4On-Site Guide factor tables held
- 2standards read back on 1.5.7, BS 5839-1:2025 and BS 5266-1:2025: every citation checked against the 2025 editions
- Last reviewed
- November 2026
- Data basis
Show the full record
On-Site Guide Appendix E factors (E1 to E4), BS 4568 conduit internal diameters (BSRIA Technical Note 10/92), PD Cable Database cable overall diameters (generic sizes from BS 7629-1:2015 Tables 2 and 3; FP200 Gold from Prysmian datasheet GB00_FP200GOLD, print of 30/09/2026), Prysmian datasheet FP200Gold/09/15 (FP200 Gold recommended clip spacing), BS 7671 Table 4D2A (FP200 Gold enclosed and clipped ratings)
- Validated against
- Conduit sizes by space factor are independently verified against calculations derived from BS 4568-1 internal diameters and IET Guidance Note 1. Version 1.9.0 was last validated on 21/11/2026, passing 77 automated checks, including 39 fault-injection tests.
- Steel, PVC or pliable conduit for single-core non-sheathed cables is sized by the On-Site Guide unit system. The space factor method uses the standard internal diameters (ID) of 16 to 32 mm steel conduit, or the manufacturer's ID entered for plastic conduit. The designer selects a sheathed cable from the PD Cable Database (BS 7629-1, FP200 Gold, Prysmian LSX, BS 6004 3-core, Belden and Cat 6A types) or enters the overall diameter of a custom cable. Only the containment is sized; the designer calculates the circuit design of record (Ib, In, Iz, voltage drop, Zs). A current-carrying capacity is given for FP200 Gold 2-core cable only, for single-phase or direct current, up to 20 circuits, with grouping and ambient factors applied. Where single-core cables share the run, the number of circuits is required for this capacity. For FP200 3-core and 4-core cables see BS 7671 Table 4D2A, Reference Method B, and for other cables their BS 7671 table.
What's changedNovember 2026 · v1.9.0Sheathed cables are now taken only from the PD Cable Database. No result is shown until the cable list has loaded. Each generic BS 7629-1 size was offered twice. These 15 sizes and FP200 Gold 2-core 1.0 mm² are now offered once, under their database names. Their overall diameters are unchanged, so no result changes, including in saved reports.
- November 2026 · v1.9.0Sheathed cables are now taken only from the PD Cable Database. No result is shown until the cable list has loaded. Each generic BS 7629-1 size was offered twice. These 15 sizes and FP200 Gold 2-core 1.0 mm² are now offered once, under their database names. Their overall diameters are unchanged, so no result changes, including in saved reports.
- November 2026 · v1.8.0Some results change: please re-check. Emergency lighting lines show a Supply field, and extra-low voltage lines an "Insulated for the highest voltage present" field. Life safety or fire-fighting (BS 8519) is a new service, checked for segregation. Runs of two or more emergency lighting lines alone now read SEGREGATION NOT CHECKED where any supply is not known. Choosing a data cable from the cable list sets a General power line to Extra-low voltage controls. In reports saved before 1.8.0, set the service of each data cable line. The fixings note now quotes BS 7671 Regulation 521.10.202 and its NOTES 2 to 5 word for word. The 1.7.0 note incorrectly limited NOTE 3 to fire-rated systems.
- November 2026 · v1.7.0Some results change: please re-check. Six FP200 Gold overall diameters are now smaller. FP200 Gold 3-core and 4-core 1.0 mm² cables are no longer offered in the cable list. Where a run holds single-core cables and a sheathed cable, enter the number of circuits for the grouping factor.
- October 2026 · v1.6.9Some results change: please re-check. Runs that passed and mix "Emergency lighting" or "Extra-low voltage controls" with another service now read SEGREGATION NOT CHECKED; fire alarm mixes still read SEGREGATE. Beyond 20 circuits, no current-carrying capacity in the run or grouping factor is given. Sizes are unchanged unless a saved cable or quantity is asked for.
- September 2026 · v1.6.8The printed report is now full size, with every page numbered. The PDF export and the emailed report no longer include the design notes; they stay in the tool and the Word, Excel, CSV and text exports, marked for the designer. The calculations, sizes and verdicts are unchanged.
- September 2026 · v1.6.7In the tool, the printed report and the exports, "Highest utilisation" now shows the run nearest its own limit, or furthest over it. In 11,826 of 38,880 two-run test reports it shows the multicore run, not the singles run; in 4,188 of those, only the singles run passed. No run's size or verdict changed. Run cards name each figure's basis.
- September 2026 · v1.6.6With Auto, the smallest conduit is 20 mm (Project Design practice from site experience), or 25 mm where set in Options; 16 mm can be chosen by hand. Runs sized at 16 mm with Auto, including the lighting radial preset, now read 20 mm: please re-check. The protective conductor notes now quote Institution of Engineering and Technology Guidance Note 1.
- September 2026 · v1.6.5The conduit space factor limit is now 35% (Institution of Engineering and Technology Guidance Note 1, Appendix A, A5). Some results change: please re-check. Runs with a sheathed cable or custom internal diameter filling 35% to 45% now read OVER 35%. In this tool, runs of singles passing the factor tables but filling over 35% now read PASS WITH WARNING.
- September 2026 · v1.6.4In the tool and the exports, the design notes give the On-Site Guide clip spacing for fire alarm and emergency lighting cables, and the manufacturer's where it differs. The drawing-in and steel conduit notes read shall, as BS 7671 does. Most acronyms are spelt out at first use. The calculations, sizes and verdicts are unchanged.
- September 2026 · v1.6.3Single-core non-sheathed runs sized by the On-Site Guide Appendix E factors are now also checked against the Guide's 45% space factor for cables not in its tables, as PD good practice. Above 45%, the verdict is PASS WITH WARNING, and a note gives the next size at 45% or less or, failing that, a split across two conduits. Where no internal diameter is held, as in PVC conduit, a note states that the space factor is not checked. Cables no longer overlap in the cross-section drawing. The sizes given with Auto and every other verdict are unchanged.
- September 2026 · v1.6.2The printed report lists the sizing steps and notes again; none had been printed since 1.5.2. Some check lines, notes and field help now read shall or should, as the clause they cite does. The green, amber and grey are now darker, for a contrast above 4.5:1 with white text (Web Content Accessibility Guidelines 2.2, level AA). The calculations, sizes and verdicts are unchanged.
- September 2026 · v1.6.1BS 7671 Regulation 521.6 is now cited for circuits sharing a conduit, not 521.7, which applies to circuits sharing a multicore cable. The BS 8519:2020 note now reads should, not need. The conduit drawings and the printed report now use the PD Power Distribution tool colours, with the four cable service colours kept. The calculations, sizes and verdicts are unchanged.
- September 2026 · v1.6.0The tool now looks like the PD Power Distribution tool, with the same font and colours. The Start again button is now in a dark bar at the top, with the tool name and version. The Cross-section and Run detail switch is now shown as tabs. The calculations, the wording of every check line, the printed report and the exports are unchanged.
- September 2026 · v1.5.8The wording in the tool was revised in plain UK English: the compliance record line and the How this works list now say in the tool, and the segregation checks are called checks. The calculations, the printed report and the exports are unchanged
- September 2026 · v1.5.7The notes written inside the program code were rewritten in plain UK English. The calculations, the wording shown in the tool, the printed report and the exports are unchanged
- September 2026 · v1.5.6The conduit is described by its internal diameter throughout: in the tool, in the help, in the check lines, in the exports and in the notes written inside the program code. Reports saved before this version open with their custom internal diameter as entered. No size, factor or limit changed
- September 2026 · v1.5.5The emergency lighting lines now cite BS 5266-1:2025 and say which wiring they apply to: a separate conduit for circuits fed from a central power supply system (8.2.6); supply cables to self-contained emergency luminaires may be installed as a normal lighting circuit (8.1). The BS 8519 fixing line now reads should, not must. No factor, size or limit changed.
- September 2026 · v1.5.4The fire alarm segregation lines now cite BS 5839-1:2025, which replaced the 2017 edition: 35.5 for the rule against sharing a conduit with other services, 35.7 for conduit to BS EN 61386 and 25.7 for the 1 mm2 conductor minimum. The earlier citation used the 2017 clause number, which in the 2025 edition covers radio-linked systems. No factor, size or limit changed.
- September 2026 · v1.5.3A sheathed or multicore run is sized on the 45% space factor whether or not the length is entered; with the length blank, a note states that the Appendix E envelope is not checked. A single-core run still needs the length. Each run has a Circuits (for Cg) field: if it is left blank, the tool's estimate is used and is now stated on the rating line; a figure entered overrides it. No factor or limit changed.
- September 2026 · v1.5.2The sizing basis is now headed How this size was reached and laid out as numbered steps for each run, with the run's size and verdict at the top of its card and every figure in bold. The steps themselves, and the report section that shows them, are the same calculations as before. No factor, size or limit changed
- September 2026 · v1.5.1The custom ID field and the custom cable overall diameter field now state what to enter: the internal diameter, not the nominal size, and the overall diameter over the sheath, not the conductor size. Where an entered ID equals a standard nominal size, or an overall diameter equals a conductor size, a check line shows the figure the tool holds; the answer is still given.
- September 2026 · v1.5.0Support spacing is now taken from all of On-Site Guide Table D3 for each run's conduit material. A run passes or fails on the 45% limit alone. A length, internal diameter, cable diameter or quantity left blank is now asked for, with no figure assumed. The ambient temperature is asked for (30 C by default), and the Table 4B1 factor is applied and stated.
- September 2026 · v1.4.3The wording was revised in plain UK English: the worst run is labelled highest utilisation, a limit is called a limit, plurals written out, empty fields show a plain hyphen and the on-screen text has no dashes. No size or factor changed
- August 2026 · v1.4.2The does-not-fit warning and banner lead with the instruction; proper plurals throughout
- August 2026 · v1.4.1The not-suitable messages now read plainly: the conduit tool is not suitable for this arrangement, please use the cable tray or cable duct tool, with the supporting numbers in a second sentence
- August 2026 · v1.4.0Where no conduit can take a run, the result now says so, with the numbers. Cables too big for conduit are named as tray or duct work, with a link to those calculators. For a run over the 45% limit at 32 mm, the figure at 32 mm is shown, as BS 4568 specifies no internal diameter above 32 mm.
- August 2026 · v1.3.1The core count numerals on the cable discs read clearly again: the white label background added in 1.3.0 no longer applies to white text on a coloured disc
- August 2026 · v1.3.0The recommended conduit sizes stay in view in a bar that follows you down the page while you edit the runs. Drawing labels have a white background so they read clearly over the cables, and a review flag on a run reads as plain text rather than a dash
- August 2026 · v1.2.0Free use is now measured in sessions: after three days of anonymous use, you enter your email address to continue free use, with no password and no account. The enclosed rating headline (the Iz and the largest device per run) is now free in the tool. The full rating table and the verbatim compliance record stay with the Engineering Toolkit.
- August 2026 · v1.1.1Subscriber-facing copy states what the Engineering Toolkit adds rather than what the free preview lacks
- July 2026 · v1.1.0Data, AV and fibre cables from the shared library can now be selected on conduit runs, sized by the 45% space factor on the datasheet overall diameter
- July 2026 · v1.0.2Run detail: the bend note now reads "bend inner radius >= 62.5 mm (2.5 x OD)" and sits clear of the saddle ticks
- July 2026 · v1.0.1Internal diameter written ID throughout; Run detail redrawn with saddles placed as the On-Site Guide places them, within 300 mm of every box and bend and then at the Table D3 maximum spacing
- July 2026 · v1.0.0First release: conduit sizing for singles by the On-Site Guide Appendix E factors (run length and bends included) and for FP200-type and LSZH multicore by the 45% space factor, with presets, fire alarm segregation, true-scale drawings and reports