CPR Cable Selector
Check a cable against the BS 7671 requirement or your specification, find what is required at a location, and verify its Construction Products Regulation (CPR) Euroclass on the Declaration of Performance (DoP). Every library row shows the source of its class.
Free to run in the tool. The Engineering Toolkit subscription adds the full cable library, the printed report, the editable Excel, Word, comma-separated values (CSV) and text exports, and the report saved to your account.
Data basis & scope
Guidance only. The manufacturer Declaration of Performance, the project specification and the designer's judgement take precedence. Verify every Euroclass on the current DoP.
- 26cables in the library, each linked to its source
- 14cables whose class is read from a Declaration of Performance (DoP) the manufacturer still lists
- 32,650scenarios pass in each tier on 2.5.6, including all 36 corridor answers
- Weeklyevery evidence link re-checked and flagged if it stops resolving
- Last reviewed
- October 2026
- Data basis
Show the full record
Of the 26 library cables, 14 have their class read from a Declaration of Performance (DoP) the manufacturer still lists, 6181B from a DoP that Doncaster no longer lists (checked 30/09/2026), 5 from manufacturer datasheets hosted with the tool, and 6 are marked DoP required
- Validated against
- Euroclass verdicts are independently verified against rules derived from BS EN 13501-6 and BS 7671 Reg 422.2.1. Version 2.5.6 was last validated on 13/10/2026, passing 32 automated checks, including 6 fault-injection tests.
- Specifies and validates a cable's reaction to fire class under the Construction Products Regulation: the Euroclass, from Aca to Fca, and its smoke, flaming droplet and acidity ratings, read from the manufacturer's Declaration of Performance rather than inferred from a datasheet.
- It classifies the cable, not the installation. The Euroclass is one input to the fire strategy, the escape route and cable requirements of BS 7671 Section 422, and any BS 8519 life safety duty, which you assess separately. A declared class is only as current as the Declaration of Performance behind it, so confirm the DoP for the exact product and issue before you specify. The designer remains responsible for the final specification.
What's changedOctober 2026 · v2.5.6An a1 class that read Compliant against either BS 7671 422.2.1 preset now reads Caution. A row whose Declaration of Performance (DoP) was read for only some sizes names them, instead of "DoP verified" (Cable library) or "Verified source:" (Check a cable). The escape route Advisory notes state a1 does not evidence the BS EN 60754-1 figure. No Euroclass changed.
- October 2026 · v2.5.6An a1 class that read Compliant against either BS 7671 422.2.1 preset now reads Caution. A row whose Declaration of Performance (DoP) was read for only some sizes names them, instead of "DoP verified" (Cable library) or "Verified source:" (Check a cable). The escape route Advisory notes state a1 does not evidence the BS EN 60754-1 figure. No Euroclass changed.
- September 2026 · v2.5.56181B, whose Declaration of Performance (DoP) Doncaster no longer lists, is labelled "DoP no longer listed" in the Toolkit Cable library and on Check a cable. Where Approved Document B is quoted, and in the non-residential corridor’s Advisory class line, its edition is named. Printed reports no longer end with a blank page; every page is numbered. No verdict changed.
- September 2026 · v2.5.4The free library count shows as verified only the 14 cables whose Declaration of Performance the manufacturer still lists, and names 6181B, whose declaration Doncaster no longer lists. In the tool, reports and exports, the Advisory class line for a non-residential common corridor names only Approved Document B (current edition) as setting no reaction-to-fire class for cables. No verdict changed.
- September 2026 · v2.5.3BS 7671 Appendix 2 Item 17 is cited instead of Building Regulations reg 7(3)(d). In general areas, two unsourced statements are replaced by BS 7671 527.1.3 and Institution of Engineering and Technology Guidance Note 1, 10th Edition, 5.5. Doncaster’s Declarations of Performance were re-read: 6491B now shows Dca-s1,d2,a1. The wording changed in the tool, reports and exports; no verdict changed.
- September 2026 · v2.5.2A residential common corridor is now Compliant only where you confirm, in three new questions, fire-resisting enclosure or all four criteria of BS 9991:2024 27.2.2, and that it is not a protected escape route; if it is, BS 7671 422.2.1 applies. At protected escape routes, s2, s3 and no smoke grade read Caution on smoke. No other verdict changed.
- September 2026 · v2.5.1Some check lines, notes and table rows now read shall or should, as the clause they cite does. The report no longer states that the BS 7671 flame test is relaxed in metal tray or metal conduit in a residential common corridor. The green, amber and grey are now darker, for a contrast above 4.5:1 with white text (Web Content Accessibility Guidelines 2.2, level AA). The classes and verdicts are unchanged.
- September 2026 · v2.5.0The tool now looks like the PD Power Distribution tool, with the same font and colours. The tool name and version are in a new dark bar at the top, with the four tabs under it. The printed report is in the new colours. The classes, the verdicts, the wording of every check line and the exports are unchanged.
- September 2026 · v2.4.2The Engineering Toolkit line now reads Free to run in the tool. The classes, the checks, the report and the exports are unchanged
- September 2026 · v2.4.1The emergency lighting note on the fire-survival circuit now cites BS 5266-1:2025: supply cables to self-contained emergency luminaires need not be fire-protected (8.1), and the wiring from a central power supply system to its luminaires should resist fire and retain circuit integrity (8.2.1). No class, test or verdict changed.
- September 2026 · v2.4.0On the Check a cable tab, the containment question is no longer asked for an outdoor or underground run: the class is whatever the project specification states, shown as a Caution line. For a corridor on that tab, the building type is no longer asked: the residential BS 9991 27.2.2 case is checked and the non-residential position is stated. The What do I need tab still has both building types. No class, test or clause changed.
- September 2026 · v2.3.1Against a required class from a specification, a bare s1 is now compared on the EN 13501-6 scale like any other smoke grade. It meets a required s1, s2 or s3, and still reads Caution against a required s1a or s1b, which include the light transmittance figure it lacks. The escape route locations under Regulation 422.2.1 are unchanged.
- September 2026 · v2.3.0A bare s1 now reads Caution because it has no light transmittance figure, and acidity a1 reads Caution with a request for the BS EN 60754-1 figure on the Declaration of Performance. The corridor and the external run are Compliant only in metal conduit, trunking or tray. The check lines were corrected against BS 7671:2018+A4:2026.
- September 2026 · v2.2.1The wording in the tool and in the report was revised in plain UK English: standards require and apply, the report names the applicable standard, plurals written out, no dashes in the on-screen text. No verdict or class changed
- August 2026 · v2.2.0Fix: the exported and emailed report was missing its body. The cable, what it was checked against, the applicable reference and the verdict are now included in the report, so the emailed summary, the printed report and the editable Excel, Word, CSV and text exports all state the check in full alongside the findings table
- August 2026 · v2.1.0Free use is now measured in sessions: after three days of anonymous use, you enter your email address to continue free use, with no password and no account. The compiled cable library is now part of the Engineering Toolkit, with a three-row sample kept free, and every verified class is still filled in automatically in the checker.
- August 2026 · v2.0.1Subscriber-facing copy now states what the subscription adds: editable Excel, Word, CSV and text exports, plus projects saved for editing later
- June 2026 · v2.0.0In the tool, the BS 7671 component tests now come first (BS EN 60332 flame, BS EN 61034-2 smoke at 60%, BS EN 60754-1 acid gas at 0.5%, added by A4:2026), with the Euroclass as the verification layer, because UK law sets no minimum class for internal wiring (BS 7671 Appendix 2 Item 17). You can now check a cable against a location or against a required class from your specification, on new tabs with validated presets.
- June 2026 · v1.2.3Power cable library expanded from Doncaster Declarations of Performance: split concentric, tri-rated, EV-Ultra, 3183Y flex and Tuff-Sheath. 26 cables
- June 2026 · v1.2.2Every datasheet-backed class now links to its source document, and the check shows the verified source for the cable you picked. 21 cables
- June 2026 · v1.2.1Print sheet fills the printable width and the cable library table renders full width; four more cables verified from their Declarations of Performance
- June 2026 · v1.2.0Print outputs the tab you are on rather than the last result; the checker and cable library become subscriber features with worked examples kept free
- June 2026 · v1.1.0Aligned to the Engineering Toolkit: editable Excel, Word, CSV and text exports and saved projects for subscribers, on a branded A4 sheet. Every Declaration of Performance link is now checked weekly and flagged when it dies
- June 2026 · v1.0.0First release: Understand, Choose, Validate and the cable library, with classes verified from Doncaster Declarations of Performance