Earthing & Bonding Selection
version 1.15.0Based on BS 7671:2018+A4:2026, IET Guidance Note 8, BSÂ 6701, BSÂ ENÂ 50310 and BSÂ ENÂ 62305-3.
Guidance only. The designer remains responsible for verifying every selection against the project specification and the current edition of BSÂ 7671 and associated standards.
About this tool
The Earthing & Bonding Selection tool is a guided decision aid built for UK electrical designers, MEP engineers and BIM coordinators working to BS 7671:2018+A4:2026.
It captures the supply earthing arrangement (TN-C-S, TN-S, TT) and the installation type, then returns the correct conductor role, minimum size, identification colour and the relevant clauses from BS 7671, IET Guidance Note 8, BS 6701 and BS EN 62305-3.
It is intended to support – not replace – the designer’s judgement. Every selection should be verified against the project specification, the DNO’s requirements and the current edition of each referenced standard.
Built and maintained by Project Design (IO). Spotted an error or want a path added? Contact us.
- 1,308 + 1,260numeric test runs on the Toolkit and free tiers on 1.15.0, no findings
- 22outcomes from 17 guided questions
- 9warnings where the answer depends on something the tool cannot see
- 24,829tool pages read by the new wording check on 1.15.0 across both tiers, no finding
- Last reviewed
- October 2026
- Data basis
Show the full record
BS 7671:2018+A4:2026 Tables 54.1, 54.7 and 54.8 for conductor sizing. The earthing conductor is sized from the line conductor under Table 54.7; on a PME supply the Table 54.8 value applies as well, and where it is buried the Table 54.1 minimum for the burial method applies as well (Reg 542.3.1): the greater value is returned. Table 54.8 is keyed on the PEN conductor of the supply, the DNO's PEN at the cut-out, service head or substation, in copper equivalent; where an installation is fed from a landlord or BNO sub-main, that sub-main has separate neutral and earth conductors and no PEN, and the DNO's PEN at the building intake is entered instead, since PME conditions apply at each installation where the intake has a PME earth terminal (ENA G87 Issue 2, 5.2 and 5.4). Main protective bonding on TN-S and TT is half the earthing conductor under Reg 544.1.1, not less than 6 mm² copper and need not exceed 25 mm² copper; on PME it follows Table 54.8 from the copper-equivalent PEN. Supplementary bonding is sized from the CPC under Regs 544.2.1 to 544.2.3, with the 4 mm² minimum without mechanical protection applied as IET Guidance Note 1 Table 3.9 does. The decision paths cite Regs 415.2.2, 542.2 to 542.4.2, 543.1.1 to 543.5.1, 544.1.1 to 544.2.5, 545.1.1 and 545.1.2, 514.4.2, 514.13.1, 708.415.1, 709.531.2, 710.415.2.101, 722.411.4.1 and 722.531.3.101, and Table 51 for conductor identification. Guidance: BS 7671 Section 545, IET Guidance Notes 1 and 8, BS 6701, BS EN 50310 and BS EN 62305-3. 17 guided questions lead to 22 outcomes, with 9 warnings raised where the answer depends on something the tool cannot see.
- Validated against
- Earthing and bonding conductor sizes are independently verified against calculations derived from BS 7671:2018+A4:2026 Tables 54.1, 54.7 and 54.8. Version 1.15.0 was last validated on 20/11/2026, passing 75 automated checks, including 27 fault-injection tests.
- A guided decision on earthing and bonding: it returns the conductor role, the minimum size, the identification and the clause behind each answer.
- Covers the three supply arrangements, TN-C-S (PME), TN-S and TT, in a building, at an EV charging point, on a caravan park or marina, at a petrol filling station and in a medical location. A TN-C-S supply with protective neutral bonding (PNB) is entered as TN-C-S (PME) where it is connected to a public network, and as TN-S where the installation is supplied only by a private network with the source earth and the neutral-earth link within the consumer's installation; where it is not known whether PME conditions apply, the results are not checked for it.
- Sizes are the table minimums. A size set by calculation under the Reg 543.1.3 adiabatic equation remains the designer's own calculation.
- The supply earthing arrangement is confirmed with the DNO. The tool works from the arrangement you state, it does not establish it.
- It supports the designer's judgement rather than replacing it. Verify every selection against the project specification, the DNO requirements and the current edition of each standard cited.
- Free to use in the tool with every answer stating its clause: three anonymous sessions, then your email continues free use, with the one page report by email. The printed report, saving to your projects and the editable exports are part of the Engineering Toolkit.
What's changedNovember 2026 · v1.15.0Some results change: please re-check. Where Table 54.7 gives a non-standard size, the result is now the next larger standard size (Reg. 543.1.4). No result for a standard line conductor changes. The supplementary bonding conductor between two exposed-conductive-parts is now the next larger standard size where the circuit protective conductor is non-standard. Every changed size is larger. The printed summary sheet (Engineering Toolkit) now shows page numbers and the references under each warning. A TT result no longer shows the note that the distributor may require 16 mm² Cu or larger.
- November 2026 · v1.15.0Some results change: please re-check. Where Table 54.7 gives a non-standard size, the result is now the next larger standard size (Reg. 543.1.4). No result for a standard line conductor changes. The supplementary bonding conductor between two exposed-conductive-parts is now the next larger standard size where the circuit protective conductor is non-standard. Every changed size is larger. The printed summary sheet (Engineering Toolkit) now shows page numbers and the references under each warning. A TT result no longer shows the note that the distributor may require 16 mm² Cu or larger.
- October 2026 · v1.14.0Earthing conductors not buried on TN-S or TT with line conductors below 4 mm² are now 4 mm² Cu, the Reg. 543.1.1 minimum outside a cable or wiring system without mechanical protection. With an 82 mm² aluminium PEN (Engineering Toolkit), results of 16 mm² are now 25 mm² Cu. The wording changed on more results, stating more cases not checked.
- September 2026 · v1.13.4The EV, caravan park or marina, and petrol filling station warnings that apply on every supply system are now also shown on TN-C-S (PME). The EV warnings now state the PME condition, the electrical separation exception and the external-influence requirements (Reg. 722.411.4.1, 722.531.3.101 and 722.512.2). The caravan park or marina warnings now state the PME prohibition (ESQCR 2002 Regulation 9(4), Reg. 708.411.4 and 709.411.4).
- September 2026 · v1.13.3On the printed summary sheet (Engineering Toolkit), every result line, worked example step, reference, designer note and warning now prints at 7 pt or more; before, the sheet was scaled to fit one A4 page, so on a long result some printed at 5.4 to 6.4 pt. A long result now continues on a second page. No size or verdict changed.
- September 2026 · v1.13.2The supplementary bonding note and the EV and caravan park or marina warnings now use the verb of their source, "shall" or "shall not", in place of "may" or "must" (BS 7671:2018+A4:2026, ESQCR 2002 Regulation 9(4)). The amber left edge of a warning that states a requirement is now darker; only its colour changed. No size or verdict changed.
- September 2026 · v1.13.1The earthing conductor note now states where the safety electrical connection label is required: at or near the connection to the earth electrode or other means of earthing (Reg. 542.3.2), and at or near the MET where it is separate from the main switchgear (Reg. 514.13.1). The main bonding note now gives the 600 mm distance from the meter outlet union "where practicable" and covers an external meter (Reg. 544.1.2).
- September 2026 · v1.13.0The tool now looks like the PD Power Distribution tool, with the same font and colours, and its name, version and the Back and Start again buttons are in a dark bar at the top. In the Engineering Toolkit, the aluminium PEN size box is now shown only after the aluminium option is chosen. No wording, clause or verdict changed.
- September 2026 · v1.12.1The wording in the tool, the result notes and the readme was revised in plain UK English. An identification note now says a conductor has no protective function (Table 51, functional earth) or performs one (Reg. 543.5.1). No table value, clause or verdict changed.
- September 2026 · v1.12.0The confirm screen after the supply and location questions is now shown only where that combination raises a warning. On a plain building on PME or TN-S it is skipped, and the role question follows directly; Back from there returns to the location question. No table value, clause or verdict changed.
- September 2026 · v1.11.0On a PME supply, the question about how the installation is supplied is no longer asked. The PEN question is now asked once, for the PEN of the DNO supply in copper equivalent; for a landlord or BNO sub-main, which has no PEN, you enter the DNO's PEN at the building intake. No table value, clause or verdict changed.
- September 2026 · v1.10.0On a PME supply, the question before the PEN entry now asks what feeds the main switch of this installation: DNO equipment or another switchboard. The worked example for the case entered now sits under a button on the result, and the fixed reference example is no longer shown. No table value, clause or verdict changed.
- September 2026 · v1.9.0In the Engineering Toolkit, the PEN questions on a PME supply now include a helper to fill in the PEN size from the DNO cable. A PEN size given in aluminium is converted to copper equivalent by conductance. The result and the worked example name the cable used. No table value, clause or verdict changed.
- September 2026 · v1.8.1On a PME supply, the question before the PEN entry now asks whether the installation is supplied direct from the DNO cut-out or from a landlord or BNO sub-main, and the sub-main answer is followed by its own PEN question. ENA G87 Issue 2 is cited at the PEN question and in the result. No value, clause or verdict changed.
- September 2026 · v1.8.0The option buttons now have shorter labels and are never cut off on a phone. The result now opens with a one-line answer, the conductor role and its size, which stays in view; the report and the printed summary sheet show the same line. No value, clause or verdict changed.
- September 2026 · v1.7.0Every result now shows a worked example for the case entered, with the table or regulation applied and the figure at each step. The fixed examples stay below it as reference examples, and the emailed and exported report shows the same steps. No value, clause or verdict changed.
- September 2026 · v1.6.1On a PME supply, the PEN input is now the copper-equivalent size of the distributor's PEN conductor at the intake (Table 54.8). A note now states that a landlord sub-main or building network cable has no PEN, and that PME conditions apply at each installation on an ENA G87 building network fed from a PME intake (G87 5.2 and 5.4).
- September 2026 · v1.6.0The supplementary bonding questions now cover what the conductor connects, whether it is mechanically protected and the CPC size. The result now gives the Reg. 544.2.1 to 544.2.3 size as a number, where before the rule was printed without a number.
- September 2026 · v1.5.3Buried earthing conductors now ask for the line conductor size (and the PEN size on PME) and return the greater of the Table 54.7 value, the Table 54.8 value where PME conditions apply, and the Table 54.1 minimum for the burial method (Reg. 542.3.1); previously the three buried options printed only the Table 54.1 minimum
- September 2026 · v1.5.2The wording was checked against the standard: the main bond need not exceed 25 mm2 (was maximum), the functional earth single-connection rule is restated to Reg. 545.1.1 without the radial wording, the green-and-yellow reservation is cited to Reg. 514.4.2, and the MET spelling in the CBN example was corrected; no value or clause number changed
- September 2026 · v1.5.1The wording in the tool was revised in plain UK English: the greater value shall be used, and maximum and minimum sizes are named as such; regulations apply and require; no value or clause changed
- August 2026 · v1.5.0Free use is now measured in sessions: three days of anonymous use, then your email continues free use with no password and no account. The report goes by email for free users; the printed report is part of the Engineering Toolkit. Every answer stays free in the tool with its clause; subscribers are unchanged
- August 2026 · v1.4.7Print summary now appears only on a result card and always prints the report sheet; previously the button showed on every step and printing before a result produced a blank page
- August 2026 · v1.4.6Full scenario audit with source read-back against the standard. PME earthing conductor now sized as the greater of Table 54.7 and Table 54.8 (new PEN question, Reg. 542.3.1); unsourced 6 mm2 floor removed; EV RCD options corrected to Reg. 722.531.3.101; BS 6701 sizing claim corrected; 544.2 and medical wording aligned to the regulations; worked examples corrected; labels quoted without dashes
- August 2026 · v1.4.5Subscriber-facing copy states what the Engineering Toolkit adds rather than what the free preview lacks
- June 2026 · v1.4.4PDF filename now matches the other tools
- June 2026 · v1.4.2Save to a project and the editable Excel, Word and CSV exports were added
- June 2026 · v1.4.0The tool was updated to BS 7671:2018+A4:2026 and the decision paths were audited again