On this page:

    Mimic Panels for Life-Safety Generators – UK-Specific Designer’s Guide

    Key takeaway: Indicator for generators and smoke-control systems (commonly referred to as ‘mimic panel’, often marked “ESP – Emergency Stand-by Power Identification Panel”) should be provided at the main fire-alarm panel and/or fire-service interface points.

    In practice, when provided, it should connect the Generator Control Panel to every Automatic Transfer Switch (ATS) and the Building Management System (BMS), where monitoring is required using fire-resistant cabling that matches the BS 8519 categories. Remember that each system must be project-specific; therefore, the designer remains free to choose the monitoring philosophy, provided the Fire Strategy demonstrates equivalence. Cat 2 fire-resistant cable is normally accepted by BSR/FRS, where ATS contacts are monitor-only (no control function).

    Overview

    This guide explains:

    • What a mimic panel is and how it is annotated on layout and schematic drawings 

    • When a mimic panel is mandatory – and when it is optional

    • Which generator signals must appear on the mimic panel.

    • Where to show voltmeter and ammeter readings to comply with BS EN 12101-10:2005 §6.3.2 and BS 8519:2020 §6.3

    • Cable, enclosure and fire-rating requirements drawn directly from UK standards.
    • Worked compliance checklists and example mimic panel datasheet.

    All recommendations presume UK practice; no overseas codes are referenced.

    What Is a Mimic Panel?

    ElementTypical Drawing SymbolPurpose in Life-Safety Context
    ESP Mimic PanelSquare with “ESP” tag on floor plan; dashed link to CIE on schematicBrigade front end for generator, smoke control, firefighting lifts
    CIE (Control & Indicating Equipment)Rectangle “CIE”Main fire alarm panel (BS 5839-1)
    ATS Status LED BlockTriangle or three stacked arrowsShows mains healthy, generator running, generator fault

    A mimic panel is a hard-wired, low-voltage fascia that repeats essential generator or smoke-control signals at the point where the fire-rescue service first assumes control. It is not a PLC HMI or BMS screen.

    When Is a Mimic Panel Required?

    Decision Matrix - example

    LocationDesignated Fire-Fighting Access Point (FFAP)?Fire-service control of life-safety systems from this point?Continuous staff presence?Visual indication should be provided?
    Main fire-control roomYesYesYesYes
    Ground-floor core entranceYesYesNoYes
    Underground car-park rampNoNoNoNo

    BS 5839-1:2025 §22.1 requires the main control & indicating equipment “close to the entrance likely to be used by the fire-rescue service”[1]. Although the BS 5839-1 §22.1 does not mention ‘mimics’, a mimic is one way to satisfy §6.3 of BS 8519 (remote indication) – note that ‘Should’ in a BSI Code-of-Practice allows an engineered alternative if it is justified and agreed; it is not an absolute legal requirement.

    Typically, however, if the entrance is not an FFAP, a mimic becomes optional.

    Generator Signals Required on the Mimic Panel

    BS EN 12101-10:2005 §6.3.2 and BS 8519:2020 §6.3 stipulate three status indicators [2] [3]:

    1. Stand-by Condition (Mains Healthy) – green LED.

    2. Generator Running – red LED.

    3. Generator Fault – amber LED.

    What about a Voltmeter and an Ammeter?

    BS 8519:2020 standard adds a second sentence: “A voltmeter and ammeter indicating the total load on the generator shall also be provided.” [3]

    The standard does not prescribe the location. Placing the instruments on the generator control panel satisfies the clause. UK project reviews show this arrangement on >90% of schemes without objection from approving authorities.

    Connecting Automatic Transfer Switches (ATS) to the BMS

    Minimum BMS I/O per ATS

    SignalTypeComment
    Mains availableDigital IN230 V relay or clean contact
    Generator availableDigital INFrom genset breaker auxiliary
    ATS position (on mains/on gen)Digital INTwo-pole feedback for SIL 2 equivalence
    ATS common faultDigital INFault/fuse fail on ATS controller
    Modbus status (optional)RS-485If manufacturer provides

    BS 8519 does emphasise dual/diverse routing (clause 7) and recommends that each critical circuit is able to survive fire; it does not expressly ban daisy-chaining low-current monitoring contacts between ATSs. However, many consultants insist on running individual circuits when the loss of a single cable would disable more than one life-safety load [3].

    Cable, Enclosure and Fire Rating Requirements

    CircuitStandard ClauseCable CategoryExample CableMin. Survival (min)
    Mimic LED feedsBS 8519 Table 1Cat 22 × 1 mm² FP200 Gold60
    ATS control & feedbackBS 8519 §11Cat 34 × 1.5 mm² FP600S120
    Generator CT/PT loopsBS 8519 §11Cat 3MICC 4 × 2.5 mm²120

    General Cable Installation Requirements

    BS 8519:2020 clause 15 (Cable installation practice) states that cables should be installed following the cable manufacturer’s recommendations [3] for fixing intervals. The standard doesn’t mandate a universal spacing.

    When 300 mm Centres ARE Required

    A 300 mm spacing requirement specifically applies to:

    1. Inverted cable management systems – as confirmed by the BEAMA guidance which states: “Where cable tray or ladder is used in an inverted orientation, cable fixings must be used with the spacings defined in Table 2”[4] – which shows 300 mm for cables up to 15 mm diameter.

    2. Fire alarm cables on inverted tray – as discussed in the Voltimum Q&A: “We are electrical contractors installing soft-skinned fire alarm cables on inverted cable tray. At the moment, we are fixing the cable at 300mm centres”[5].

    3. Cables not supported by metal containment – where cables are clipped directly to building fabric, manufacturer recommendations typically suggest 300 mm horizontal/400 mm vertical spacing [5].

    Mimic Panel Hardware Specification (UK Practice)

    FeatureRequirementReference
    LED legends engraved in English“MAINS ON”, “GEN ON”, “FAULT”BS 8519 Fig 1
    Lamp-test push-buttonMomentary, shroudedFIA CIE Guidance p.9
    PSUEN 54-4, 72 h standbyBS 5839-1 Table 11
    Enclosure ratingIP 55, RAL 7035 steelBS EN 60529
    Cable entryGland plate undersideBS 7671 18th Ed.

    Compliance Checklist

    ItemDesign StageVerified (✓)
    FFAP locations confirmed in Fire StrategyRIBA Stage 2  
    Mimic panel only at FFAPStage 3  
    Generator control panel fitted with V & A metersStage 3  
    Three mimic LEDs wired via clean contactsStage 4  
    Each ATS wired back to BMS with Cat 3 or Cat 2 cable[*]Stage 4  
    Cabling routes enclosed 120 minStage 4  
    EN 54-4 PSU autonomy test certificateStage 5  
    Cause-and-effect matrix references mimic I/OCommissioning  

    [*] Each ATS wired back to BMS with Cat 3 cable (or Cat 2 where monitor-only, subject to risk assessment).

    Mimic Panel example

    Maintenance Regime (per BS 5839-1 & BS 8519)

    TaskIntervalStandard
    Lamp-test and LED visual checkWeeklyBS 5839-1 §44
    Simulated mains failure (ATS test)MonthlyBS 8519 §6.3 Note 3
    Generator load-bank test incl. V & A readingAnnualBS EN 12101-10 Test 12.1
    Cable clamp & gland inspection3-yearlyBS 8519 §12.3

    Template Specification Clause

    Provide an ESP mimic panel adjacent to the main Control & Indicating Equipment.
    The panel shall display, via hard-wired LEDs, Mains Healthy (green), Generator Running (red) and Generator Fault (amber).
    Voltmeter and ammeter shall be integral to the generator control panel.
    ATS status and fault contacts shall be wired in Category 3 fire-resistant cable to the BMS and mimic panel.
    Panel supply shall be 24 V d.c. from an EN 54-4 power unit with 72 h standby.
    Enclosure: IP 55, RAL 7035, 1.5 mm steel, minimum 300 × 300 × 150 mm.

    On This page

      Leave a Reply

      Your email address will not be published. Required fields are marked *

      share this page