This trunking size calculator works to BS 7671 and the On-Site Guide Appendix E.

PD Trunking

version 1.7.0

Size a cable trunking for the cables it must hold: singles by the On-Site Guide Table E5/E6 factors, sheathed and multicore cables by the 45% space-factor method. Print the record that proves it.

Grounded in BS 7671OSG Appendix EBS 5839-1BS 5266-1BS 8519
How this works
  1. Add a trunking section. A section is one trunking size on one route: set its material, size (or Auto), orientation and compartments, then drop cables in, or pick a typical situation and edit it.
  2. The method follows the cable type. Single-core non-sheathed cables (BS 6004 PVC / BS 7211 LSZH) use the exact On-Site Guide Table E5 factors against the Table E6 trunking factors, extended to 240 mm² by the ESC tables. Sheathed and multicore cables use the 45% space-factor rule, with flat twin-and-earth taken as a circle of diameter equal to its MAJOR axis, as the Guide states. Both include your spare-capacity margin.
  3. Read the verdicts and print the record: trunking size per section, the factor or space-factor calculation, the segregation and compartment checks (where fire alarm cables share the trunking, a partitioned compartment reserved solely for them), the grouping consequence an internal barrier does NOT remove, and the drawings.

Free to run for everyone. Engineering Toolkit subscribers get the compliance record with verbatim clause citations, the in-trunking rating check, editable Excel / Word / CSV / Text exports and My Projects.

Add a trunking section
Trunking drawing Cross-section Run detail

Recommended trunking: -
Sections0
Cables0
Highest utilisation-
Method-
Support spacing-
Circuits → Cg-
How this size was reached
In-trunking current rating: the grouping consequence
Compliance record: the clauses, quoted verbatim
Design notes
v1.7.0 · Verified IET On-Site Guide Appendix E (Tables E5/E6), ESC Technical Manual T113-1 and T113-3, BS 7671:2018+A4:2026 (521.5.1, 521.6, 521.10.1, 521.10.202, 527.2.2, 528.1, Reference Method B, Table 4C1), BS 5839-1:2025 35.5, BS 5266-1:2025 8.2.6, BS 8519 cl. 15/16 and Annex B
  • 1,538scenarios enumerated in each tier on 1.4.2, recomputed from the source tables
  • 37 of 37steel factors verified against Table E6
  • 1.5 to 240 mm2single-core range sized by the factor method
  • 0findings on the 1.4.2 re-run, both tiers
Last reviewed
November 2026
Data basis
IET On-Site Guide Appendix E (Tables E5/E6, the 45% space factor rule with the major-axis definition); ESC Technical Manual T113-1, July 2008, and T113-3, March 2009 (cable factors...Show the full record

IET On-Site Guide Appendix E (Tables E5/E6, the 45% space factor rule with the major-axis definition); ESC Technical Manual T113-1, July 2008, and T113-3, March 2009 (cable factors extended to 240 mm2, spare capacity rule, internal areas); BS 7671 (521.5.1, 521.6, 521.10.1, 521.10.202, 527.2.2, 528.1, Appendix 4 Reference Method B and Tables 4B1, 4C1 and 4D2A); BS 5839-1:2025 35.5, BS 5266-1:2025 8.2.6, BS 8519 cl.15/16 and Annex B; Legrand Salamandre 2019 standard range; MK PVCu 45% areas; multicore cable overall diameters, except the flat twin and earth 2.5 mm2 cable, from the PD Cable Database (Prysmian FP200 Gold datasheet GB00_FP200GOLD, print of 30/09/2026; Prysmian LSX datasheet, print of 02/11/2026; BS 7629-1:2015 Tables 2 and 3; ESC Technical Manual T113-1 Worked example 1); OSG Table D4 supports; Quelfire tested firestop details.

Validated against
Fill and support spacing are independently verified against calculations derived from IET On-Site Guide Tables E5, E6 and D4 and stored data. Version 1.7.0 was last validated on 20/11/2026, passing 74 automated checks, including 23 fault-injection tests.
Scope and limits
  • Sizes trunking sections for single-core cables (BS 6004 PVC / BS 7211 LSZH, 1.5 to 240 mm2) by the Table E5/E6 factors and for sheathed, multicore and flat cables by the 45% space factor. Auto proposes manufacturer standard sizes; any Table E6 or custom internal size can be checked. Compartment capacity is split equally unless the compartment widths are entered: confirm real compartment areas from the catalogue. PVCu capacities are the manufacturer 45% areas; a fire-rated (BS EN 1366-5) system is sized only on the manufacturer's internal size and support centres that you enter. The grouping factor uses an estimated or user-entered circuit count up to the 20 circuits Table 4C1 tabulates. This tool checks the containment. The circuit design of record (Ib, In, Iz, voltage drop, Zs) remains the designer's. For FP200 Gold cables, the in-trunking rating shown is the BS 7671 Table 4D2A figure with the Table 4B1 ambient temperature factor (25 to 50 °C) and the Table 4C1 grouping factor. Other cables are referred to their BS 7671 table.
What's changedNovember 2026 · v1.7.0The PD Cable Database is now the only source of round multicore cables. No result is shown until the cable list has loaded. The 20 cables previously stored in the tool are now database rows with the same overall diameters, so no result changes. Their database names are used in the list, the printed report and the exports.
  • November 2026 · v1.7.0The PD Cable Database is now the only source of round multicore cables. No result is shown until the cable list has loaded. The 20 cables previously stored in the tool are now database rows with the same overall diameters, so no result changes. Their database names are used in the list, the printed report and the exports.
  • November 2026 · v1.6.0Some results change: please re-check. FP200 Gold overall diameters are now the Prysmian datasheet GB00_FP200GOLD figures; six are smaller. The 3-core and 4-core 1.0 mm² cables are no longer offered. Select the project ambient temperature, 25 to 50 °C. The FP200 Gold current-carrying capacity in the trunking now includes its BS 7671 Table 4B1 factor. FP200 Gold 3-core and 4-core cables now have a Table 4D2A current-carrying capacity for 3 loaded conductors, or 2 where chosen on the cable line. The clipped rating is removed from the tool, the printed report and the exports. Reports saved before 1.6.0 open at 30 °C and 3 loaded conductors and list each changed diameter.
  • November 2026 · v1.5.1The calculations and results are unchanged. Cross-section labels now fit their column in the tool, the printed report and the exports. The fire alarm compartment lines state the BS 5839-1:2025 35.5 condition: where fire alarm cables share common trunking. BS 4678-1 and BS 4678-4 are shown as withdrawn. The greyed Engineering Toolkit panels on the free page show placeholder characters.
  • October 2026 · v1.5.0Some results change: please re-check. The tool is renamed PD Trunking. Sections that passed with a cable size missing read ENTER CABLE SIZE, with no estimated grouping factor; some others read SEGREGATE, SEGREGATION NOT CHECKED or NOT CHECKED. 3-core and 4-core FP200 get no current-carrying capacity. Circuit estimates count 2 singles per circuit, not 3: grouping factors can be lower.
  • September 2026 · v1.4.2The printed report lists the sizing steps and the check lines marked NOTE again; none had been printed since 1.3.2. Some check lines, notes and help now read shall, should or must, as the clause they cite does. The green, amber and grey are now darker, for a contrast above 4.5:1 with white text (Web Content Accessibility Guidelines 2.2, level AA). The calculations and results are unchanged.
  • September 2026 · v1.4.1BS 7671 Regulation 521.6 is now cited for circuits sharing trunking, not 521.7, which applies to circuits sharing a multicore cable. The note on steel trunking as the protective conductor now cites Regulation 543.2.5, not 543.2.2. The drawings now use the PD Power Distribution tool font and colours, with the cable service colours kept. The calculations and results are unchanged.
  • September 2026 · v1.4.0The tool now looks like the PD Power Distribution tool, with the same font and colours. The tool name and version are in a dark bar at the top, with the Start again button. The Cross-section and Run detail switch is now a row of tabs. The calculations, every result, the drawings, the printed report and the exports are unchanged.
  • September 2026 · v1.3.8The wording in the tool was revised in plain UK English: the compliance record line and the How this works list now say in the tool, and the segregation and compartment checks are called checks. The calculations, the printed report and the exports are unchanged
  • September 2026 · v1.3.7The notes written inside the program code were rewritten in plain UK English. The calculations, the wording shown in the tool, the printed report and the exports are unchanged
  • September 2026 · v1.3.6The emergency lighting lines now cite BS 5266-1:2025: the partition in shared trunking (8.2.6), the marking of reserved trunking (8.2.5) and the non-combustible support (8.2.3) apply to luminaires fed from a central power supply system; supply cables to self-contained emergency luminaires may be installed as a normal lighting circuit (8.1). The segregation and fixing lines now read should, not must. No factor, size or limit changed.
  • September 2026 · v1.3.5The fire alarm lines now cite BS 5839-1:2025, which replaced the 2017 edition: 35.5 for the compartment rule, 35.7 for non-metallic trunking to BS EN 50085-1, 25.7 for the 1 mm2 conductor minimum, 25.9 for the single cable colour and 35.3 for cable support. Two statements were corrected against the 2025 text: non-metallic trunking in a fire alarm system should conform to BS EN 50085-1, not BS 4678-4, and plastic trunking as the sole support of fire alarm cables is likely to be precluded, not precluded outright. No factor, size or limit changed.
  • September 2026 · v1.3.4The storey height field shows only on a vertical section that penetrates a fire-rated element, which is the only case that reads it (the slab crossing positions in the run detail). No factor, size or limit changed
  • September 2026 · v1.3.3A new section now starts with the length blank. Before, every section started at 6 m, which was printed as if it had been entered, and a vertical section left at 6 m was given a check line to provide intermediate supports. The support count, the pin racks and the fire-stopping positions are given once the length is entered. No factor, size or limit changed.
  • September 2026 · v1.3.2The sizing basis is now headed How this size was reached and laid out as numbered steps for each section, with the section's size and verdict at the top of its card and every figure in bold. The steps themselves, and the report section that shows them, are the same calculations as before. No factor, size or limit changed
  • September 2026 · v1.3.1The custom internal width and depth fields and the custom cable diameter field now state what to enter: the internal dimensions, not the catalogue size, and the overall diameter over the sheath, not the conductor size. Where a steel or PVCu entry equals a standard size, or an overall diameter equals a conductor size, a check line shows the figure the tool holds; the answer is still given.
  • September 2026 · v1.3.0A fire-rated system is now sized on the manufacturer's internal dimensions only, with its supports at the manufacturer's tested centres. The FP200 Gold rating table now applies only to FP200 cables; for every other cable, the rating is referred to its own BS 7671 Appendix 4 table. A spare capacity or length left blank is now asked for, with no figure assumed, and a spare above 60% is refused.
  • September 2026 · v1.2.3The result summary and report title name the section with the highest utilisation; the trunking cover rule is cited to BS 7671 Reg 530.4.3 rather than Section 530. No size or factor changed
  • September 2026 · v1.2.2The wording was revised in plain UK English: the worst section is labelled highest utilisation, a limit is called a limit, plurals written out, the on-screen text has no dashes. No size or factor changed
  • August 2026 · v1.2.1The core count numerals on the cable discs read clearly again: the white label background added in 1.2.0 no longer applies to white text on a coloured disc
  • August 2026 · v1.2.0The recommended trunking sizes stay in view in a bar that follows you down the page while you edit the sections. Drawing labels have a white background so they read clearly over the cables, and a review flag on a section reads as plain text rather than a dash
  • August 2026 · v1.1.0Free use is now measured in sessions: after three days of anonymous use, you enter your email address to continue free use, with no password and no account. The in-trunking rating headline (the Iz and the largest device per section) is now free in the tool. The full rating table, the circuit count basis and the verbatim compliance record stay with the Engineering Toolkit.
  • August 2026 · v1.0.8Subscriber-facing copy states what the Engineering Toolkit adds rather than what the free preview lacks
  • July 2026 · v1.0.7Claims audit: the Reg 527.2.3 note said every listed size exceeds 710 mm² internally, which is wrong, and is corrected (the three smallest PVCu mini-trunking sizes fall below it); the non-standard-size note now cites the 18-size Salamandre range precisely
  • July 2026 · v1.0.6Vertical risers gain a storey height input (default 4 m) that places the floor slabs and their internal fire seals in the run detail. Capacity unchanged
  • July 2026 · v1.0.5Run detail: the firestop support rule moved to its own line, clear of the length dimension on risers
  • July 2026 · v1.0.4Identical notes raised by several sections now merge into one card, headed SECTION 1 & SECTION 2
  • July 2026 · v1.0.3Auto sizing proposes manufacturer standard sizes only (Legrand Salamandre, 18 sizes), with the other Table E6 sizes still selectable; new per-section circuit count for Cg, with the counting basis stated
  • July 2026 · v1.0.2Fire-rated crossings show the tested-detail support rule: independent supports both sides of every seal, the first bracket within 400 mm of each seal face, so no load transfers onto the firestop
  • July 2026 · v1.0.1Run detail: the DB origin is drawn with the standard distribution board symbol
  • July 2026 · v1.0.0First release: trunking sizing to BS 7671 and the On-Site Guide Appendix E. Singles by the Table E5/E6 factors to 240 mm², sheathed and multicore by the 45% space factor with the major-axis rule, plus compartment partition checks, vertical riser support, true-scale drawings and reports