On this page:

    Domestic PV sizing rule-of-thumb (RoT)

    Grid-tied, focused on self-consumption

    1. UK rule-of-thumb (RoT) Peak Sun Hours (PSH): 3.5 summer, 2.0 spring/autumn, 1.0 winter
    2. For calc use Peak Sun Hours (PSH) = 2 h for UK spring/autumn.
    3. Assume a typical house uses 10 kWh/day, of which 6 kWh at the evening.

     

    PV size = daily kWh ÷ PSH × 1.3 = 10 ÷ 2 × 1.3 = 6.5 kWp.

    *1.3 PV factor

    Battery nominal

    Evening kWh ÷ Depth of Discharge DoD (0.85) × small losses (approx. 1.1)

    = 6 × 1.1 ÷ 0.85 = 7.8 kWh = rounded up 8 kWh.

    1. Battery: 8 kWh nominal gives enough usable energy to run an average evening
    2. Battery usable capacity ≈ nominal × DoD = 8 kWh × 0.85 ≈ 6.8 kWh.
    3. Inverter: A 5 kW hybrid inverter will handle daytime loads;

     

    RoT panels Qty: 15–16 panels (420–440 W panels).

    Export limits

    UK DNO permissions (G98/G99) may cap inverter export (e.g., 3.68 kW single-phase). Meaning larger batteries or export-limiting inverters

    Orientation

    1. South‑facing array (typical UK pitch ~30–40°): generation rises quickly in the morning, peaks hard at solar noon, then drops. Watts concentrated in a few hours.
    2. East/West split: half of the panels look east (morning), half west (afternoon). You get two lower humps with a dip at noon. Net effect: longer, flatter output across the day – better for self‑use.
    On This page

      Leave a Reply

      Your email address will not be published. Required fields are marked *

      share this page