On this page:

    Electrical & Mechanical Equipment: Access & Maintenance (UK)

    TL;DR

    • There is no universal “1 m rule” in UK law or BS 7671. The legal duty is to provide adequate working space, access and lighting (EAWR Reg. 15). Legislation.gov.uk

    • Numbers appear when you’re in restricted-access electrical rooms (BS 7671 Section 729: operating/maintenance gangways) and from manufacturer instructions. electrical.theiet.org+1

    • Some sectors/clients (e.g., UK water industry via WIMES) do require ~1 m clearance — that’s client/sector spec, not law. pumpcentre.com+1

    1. What the law actually requires (baseline for every project)

    • EAWR Reg. 15: provide adequate working space, adequate means of access and adequate lighting at electrical equipment where work may give rise to danger. This is your non-negotiable legal anchor for layouts and clearances. Legislation.gov.uk

    • CDM 2015 (designer duty): design to eliminate, reduce or control foreseeable risks; provide enough information with the design so others can comply. (Use this to justify room sizing, door swing, heavy-item removal routes, etc.) Legislation.gov.ukHSE

    • HSG85: practical HSE guidance on safe working around electrical gear (planning, safe access/space, lighting). Use it to evidence your maintenance reasoning alongside EAWR. HSEhealthandsafety-services.co.uk

    • Fire service access overlay (ADB B5): coordinate plant room locations and external access with the vehicle access rules (e.g., a door every ≤ 60 m on accessible elevations; min 750 mm door width). GOV.UK

    2. When BS 7671 gives you actual numbers

    In restricted-access electrical rooms (e.g., switchrooms, locked plant areas/roofs reserved for skilled/instructed persons), BS 7671 Section 729 sets minimum gangway/working-space envelopes and related conditions for operation and maintenance. Typical design outcomes include:

    • Baseline gangway (barriers/enclosures as basic protection)
      – Working width around ≥ 700 mm
      Headroom around ≥ 2000 mm
      – Keep live parts out of normal reach (often taken as ≥ 2500 mm).

    • Encroachment while doors are open / withdrawable gear
      – Preserve a passing width during maintenance, keep safe door swing (≥ 90°) and working depth at fronts.

    • Long line-ups, exits & doors
      – Long gangways should be accessible from both ends (triggered around 10–20 m depending on room geometry and dooring); doors/hinged panels to open ≥ 90°.

    These are BS 7671 figures/conditions specific to restricted areas. Always check the current edition (and any manufacturer overlay). electrical.theiet.org+1

    • If protective measure is barriers/enclosures → 700 mm / 2000 mm / 2500 mm.

    • If unprotected live parts (one side) → 900 mm gangway; 700 mm in front of controls; 2500 mm to live parts.

    • If live parts on both sides → 1300 mm between live parts; 1100 mm min from handle to opposite live parts; 900 mm free in front of controls; 2500 mm to live parts. Iteh Standards

    Restricted vs. open‑access context (who the room is for) 

    • Restricted access areas must be signed and kept locked to skilled or instructed persons only; unauthorised persons must not have access. (This is the premise for applying Section 729 numbers to panel/DB rooms.) Iteh Standards

    End wall clearance for long runs

    • For long line‑ups, place equipment a minimum of 700 mm from end walls (or provide a second door) so gangways > 10 m are accessible from both ends. Closed restricted‑access areas > 20 m must have doors at both ends. Iteh Standards

    Isolation & emergency switching (applies to all panels/DBs)

    • Ensure suitable means are available for cutting off the supply and for isolation; “isolation” means secure disconnection and separation from every source of electrical energy. (Position, labelling and access to these devices must reflect the EAWR duty.) Legislation.gov.uk

    Consumer units / DBs in general spaces: Where boards are not in restricted rooms (e.g., riser cupboards serving common parts), lean on EAWR 15 + manufacturer’s instructions for safe working space and isolation reach; avoid inventing numeric “working depth” unless the OEM specifies one. Legislation.gov.ukIET Electrical

    However, in dwellings, advice on mounting height for equipment not intended for regular user interaction (like meter cupboards, consumer units or router, etc.)

    “Reasonable provision should be made to ensure that the approach route to any communal facilities that serve the dwelling meets these provisions. Communal facilities include storage areas, such as those used for depositing refuse and recycling, but not plant rooms or other service areas unless occupants need regular access, for example for meter reading.” ADM Section 2A Clause 2.4

    Consumer units are mounted so that the switches are 1350-1450mm above floor level” ADM Clause 1.18

    3. Access during maintenance (doors/withdrawable gear)

    Maintain a minimum passing width of 700 mm in use. Where doors can be fixed open or circuit-breakers are fully withdrawn, keep ≥ 500 mm to the opposite limitation.

    4. Length, exits and door geometry

    • Gangways > 10 m shall be accessible from both ends; closed restricted‑access areas > 20 m shall be accessible by doors from both ends. Doors/hinged panels shall open to ≥ 90°.”

    • Doors giving access to closed restricted areas must allow evacuation to the outside without the use of a key or tool, and gangways must allow equipment doors/panels to open to ≥ 90°. (Outward opening is strongly recommended and often adopted to facilitate evacuation.)

    5. Where “1 m clearance” comes from

    credit: Dan Oxford

    The Water Industry Mechanical and Electrical Specifications WIMES 3.02 Low Voltage Electrical Installations extends the BS7671 access requirement to 1000mm 

    “The minimum distance specified for the width of a maintenance gangway in Section 729 of BS 7671 is 700 mm, however, extending this to 1000 mm in this Specification is considered a reasonable measure to facilitate all foreseeable Assembly installation, operation and maintenance activities.” WIMES 3.02 – Low Voltage Electrical Installations Clause 3.3.5

    Manufacturer’s instructions

    The selection/erection must take account of manufacturer’s instructions. If an OEM or specification calls for ≥ 1000 mm frontal working depth, that becomes the project requirement over and above the 700 mm minimum, for example : https://www.se.com/uk/en/faqs/FA32222/

    6. Firefighting access (layout coordination)

    Provide reasonable facilities to assist fire-fighters and reasonable provision within the site for fire appliance access. Use this to coordinate plant-room locations, switchgear access routes and external yard clearances with ADB B5. GOV.UK

    • For small buildings: provide access to the lesser of 15% of perimeter or within 45 m of every footprint point.

    • Each accessible elevation to have doors at ≤ 60 m spacing (min 750 mm wide).
      clause 15.3. GOV.UK

    7. Practical layout rules

    Step 1 — Classify the space

    • Restricted-access electrical rooms/areas (switchrooms, risers, plant decks; skilled/instructed persons only): apply BS 7671 Section 729 for operating/maintenance gangways and working space (plus OEM instructions).

    • General access areas: default to EAWR Reg. 15 (adequate working space, access and lighting) and HSG85 safe-working guidance. Legislation.gov.ukHSE

    Step 2 — Overlay Part M correctly

    • Dwellings (Volume 1): where Part M applies, keep wall-mounted switches/sockets within 450–1200 mm A.F.L., and mount consumer unit switches 1350–1450 mm A.F.L. (Diagram 1.5). GOV.UK

    • Buildings other than dwellings (Volume 2): apply the accessibility objectives in user-facing spaces. But: Requirement M1 does not apply to any part of a building used solely to enable the building or any service or fitting to be inspected, repaired or maintained — i.e., plant rooms/risers aren’t Part M spaces. Use EAWR/HSG85 + BS 7671/OEM there. GOV.UK

    Step 3 — Overlay manufacturer & client/sector specs

    • If the OEM asks for >700 mm or a specific service envelope (e.g., to withdraw ACBs), use that (BS 7671 510.3 principle).

    • If the client/sector has a standard (e.g., WIMES in the water industry specifying ~1 m around LV assemblies), adopt it as a project requirement.

    Step 4 — Egress & doors during maintenance

    • Maintain safe egress while panels/doors are open. Keep a usable passing width with doors/panels at ≥90° and plan working space so operatives aren’t forced into live zones. (Use your BS 7671 Section 729 logic for restricted rooms and OEM service envelopes for each assembly.)

    • Two-way access for long line-ups. Where gangways are long or end-blocked by withdrawable gear, provide access from both ends (apply your Section 729 criteria).

    • Fire service access (ADB overlay). Where relevant to the plant location, check external door spacing/widths to support FRS access/egress.

    • If your client/sector adopts WIMES 3.02 (water industry): treat ~1 m clearance around LV assemblies as a hard constraint to allow:

      • full door opening and safe operator stance,

      • withdrawal of ACBs/draw-out units for routine maintenance,

      • a clear emergency escape route in front of the assembly.
        Show the 1 m envelope on GAs/elevations, keep it free of other services/cable ladders, and reference it in your room data sheet/spec. (WIMES is a client/sector specification, not legislation—apply where the project requires it; thanks to Dan Oxford for flagging this nuance.)

    Step 5 — Record the rationale (CDM)

    • In the design risk register/spec: state the room classification, the rule-set applied (EAWR/HSG85/BS 7671/Part M/OEM/WIMES), how evacuation is maintained during maintenance, and show removal routes for heavy components.

    8. Means of escape for fire safety

    Part B of the Building Regulations (England) sets fire safety requirements for building work.
    Approved Document B gives guidance:

    • Volume 1 — dwellings

    • Volume 2 — non-dwellings

    Tables 8–10 apply to non-dwellings.
    Other approaches may be valid—check with the project’s fire safety consultant and building control body.

    Minimum widths of escape routes and exits

    Maximum number of peopleMinimum width
    60750 mm
    110850 mm
    2201,050 mm
    More than 2205 mm per person

    Minimum number of escape routes and exits from a room, tier or storey

    Minimum number of peopleMinimum number of escape routes
    601
    6002
    more than 6003

    Maximum travel distance for escape

    Type of buildingMaximum travel distance for escape available in one directionMaximum travel distance for escape available in at least two directions
    Residential (institutional)9 m18 m
    Residential (other) in bedrooms [i]9 m18 m
    Residential (other) in bedroom corridors [ii]9 m35 m
    Residential (other) elsewhere18 m35 m
    Offices18 m45 m
    Shop and commercial premises18 m45 m
    Assembly and recreation buildings primarily for disabled people9 m18 m
    Assembly and recreation buildings with fixed seating in rows15 m32 m
    Assembly and recreation buildings (elsewhere)18 m45 m
    Industrial buildings, storage and other non-residential (normal hazard) [iii]25 m45 m
    Industrial buildings, storage and other non-residential (higher hazard) [iii]12 m25 m
    Place of special fire hazard [iv]9 m [v]18 m [v]
    Plant room or rooftop plant (distance within the room)9 m35 m
    Plant room or rooftop plant with escape route not in open air (overall travel distance)18 m45 m
    Plant room or rooftop plant with escape route not in open air (overall travel distance)60 m100 m

    Notes:
    [i] Maximum part of travel distance within the room. This limit applies within the bedroom and any associated dressing room, bathroom or sitting room, etc. The distance is measured to the door to the protected corridor that serves the room or suite.
    [ii] Maximum part of travel distance applying from that point along the bedroom corridor to a storey exit.
    [iii] The appropriate travel distance depends on the level of fire hazard associated with the processes and materials being used. For the definition of higher hazard, refer to Approved Document B Volume 2[7].
    [iv] This is defined as a room such as an oil-filled transformer room, switch gear room, boiler room, storage space for fuel or other highly flammable substances or a room that houses a fixed internal combustion engine.
    [v] Maximum part of travel distance within the room/area. Travel distance outside the room/area should comply with the limits for the purpose group of the building or part.

    General note:
    If the internal layout of partitions, fittings, etc. is not known, direct distances, rather than travel distances, should be assessed. The direct distance should be assumed to be two-thirds of the actual travel distance.

    9. Human factors & reach distances

    Maintenance reach levels: Maximum 2100mm above floor level

    Passageway:
    – Height: 2100 mm minimum
    – Passageway width: 550 mm minimum – 750mm optimum

    Working positions:
    – Standing work: 900 mm – 1.5m working height optimum
    – Kneeling: 600 mm – 1.2 m working height

    Access routes:
    – Passageways: 550 mm minimum, 750 mm optimum 
    – Stairs: 600 mm to 750mm one person, 1.1 m minimum, two people. 

    Source: BS 8313 as amended in BSRIA BG 55

    Image Source: Based on BS 8313 and amended in BG 55

    10. BG 84_2024 Space planning allowances (early design stage)

    During concept design and feasibility studies, use industry-standard space and weight allowances to size plant rooms, coordinate structural loads, and verify access routes before detailed equipment selection. These rule-of-thumb allowances from BSRIA BG 84/2024 provide approximate space envelopes for common building services equipment, including maintenance access, concrete bases, cable/pipe clearances, and heat dissipation zones.

    Key applications:
    Plant room sizing during architectural coordination
    Structural loading estimates for slab design
    Access route planning for equipment delivery and replacement
    Space budgeting across mechanical and electrical disciplines

    Important: These are preliminary allowances only. Always verify with manufacturer datasheets, detailed calculations, and current standards during detailed design stages. The responsibility for safe and appropriate application rests with qualified professionals.

    The following table consolidates key clearance requirements from construction industry data and British Standards:

    CategoryEquipmentClearance_TypeDimensionLocationNotesReference
    Equipment InstallationBiomass BoilersBase allowance150 mmBelowConcrete base allowanceFigure 1 - Biomass boiler plant room area and height
    Equipment InstallationAir Cooled CondensersBase and anti-vibration mounts300 mmBelowBase and anti-vibration mounts allowanceFigure 4 - Air cooled condensers area and height
    Equipment InstallationAir Cooled CondensersHeat dissipation clearanceClear height requiredAboveClear height above units must be provided for vertical air discharge to allow heat to dissipateFigure 4 - Air cooled condensers area and height
    Equipment InstallationAir Handling UnitsBase and condensate trap200 mmBelowBase and condensate trap allowanceFigure 6 - Air handling units area and height
    Equipment InstallationAir Handling UnitsCrawl space above unit790 mmAboveCrawl space above each unit for maintenance accessFigure 6 - Air handling units area and height
    Equipment InstallationGas Fired BoilersBase allowance150 mmBelowConcrete base allowanceFigure 8 - Gas fired boiler plant room area and height
    Equipment InstallationHorizontal CalorifiersBase allowance100 mmBelowConcrete base allowanceFigure 10 - Horizontal calorifiers area and height
    Equipment InstallationHorizontal CalorifiersPipework clearance1,000 mmAboveHeight allowance for pipeworkFigure 10 - Horizontal calorifiers area and height
    Equipment InstallationVertical CalorifiersBase allowance100 mmBelowConcrete base allowanceFigure 12 - Vertical calorifiers area and height
    Equipment InstallationVertical CalorifiersPipework clearance1,000 mmAboveHeight allowance for pipeworkFigure 12 - Vertical calorifiers area and height
    Equipment InstallationAir Cooled ChillersBase and anti-vibration mounts300 mmBelowBase and anti-vibration mounts allowanceFigure 14 - Air cooled chillers area and height
    Equipment InstallationAir Cooled ChillersHeat dissipation clearanceClear height requiredAboveClear height above units must be provided for vertical air discharge to allow heat to dissipateFigure 14 - Air cooled chillers area and height
    Equipment InstallationWater Cooled ChillersBase and anti-vibration mounts300 mmBelowConcrete base and anti-vibration mounts allowanceFigure 16 - Water cooled chillers area and height
    Equipment InstallationForced Draught Cooling TowersBase allowance200 mmBelowBase allowance for foundationFigure 18 - Forced draught cooling tower area and height
    Equipment InstallationForced Draught Cooling TowersHeat dissipation clearanceClear height requiredAboveClear height above units for vertical air discharge to allow heat to dissipateFigure 18 - Forced draught cooling tower area and height
    Equipment InstallationInduced Draught Cooling TowersBase allowance200 mmBelowBase allowance for foundationFigure 20 - Induced draught cooling tower area and height
    Equipment InstallationInduced Draught Cooling TowersHeat dissipation clearanceClear height requiredAboveClear height above units for vertical air discharge to allow heat to dissipateFigure 20 - Induced draught cooling tower area and height
    Equipment InstallationCold Water Storage TanksBase allowance150 mmBelowConcrete base allowanceFigure 22 - Cold water storage area and height
    Equipment InstallationCold Water Storage TanksFreeboard height500 mmAbove water levelFreeboard height allowance above maximum water levelFigure 22 - Cold water storage area and height
    Equipment InstallationCold Water Storage TanksCrawl space above tank790 mmAboveCrawl space above tank for maintenance accessFigure 22 - Cold water storage area and height
    Equipment InstallationCold Water Storage Tanks (External Flange)Additional height for external flange500 mmAboveAdditional height allowance if externally flanged tank is usedFigure 22 - Cold water storage area and height
    Equipment InstallationDiesel GeneratorsBase and anti-vibration mounts300 mmBelowConcrete base and anti-vibration mounts allowanceFigure 24 - Diesel generators area and height
    Equipment InstallationDiesel GeneratorsCrawl space above unit790 mmAboveCrawl space above unit for maintenance accessFigure 24 - Diesel generators area and height
    Equipment InstallationHybrid Rotary UPSBase allowance100 mmBelowConcrete base allowanceFigure 26 - Hybrid rotary UPS area and height
    Equipment InstallationHybrid Rotary UPSCable installation height1,000 mmAboveHeight allowance for cable installationFigure 26 - Hybrid rotary UPS area and height
    Equipment InstallationStatic UPSCable installation spaceAdditional space requiredTop and bottomAdditional space should be provided at top and bottom for cable installationFigure 28 - Static UPS area and height
    Equipment InstallationStatic UPS (≥400 kVA)Cooling clearance400 mmAboveAdditional clearance at top for cooling purposes for UPS rated 400 kVA or aboveFigure 28 - Static UPS area and height
    Equipment InstallationStatic UPSRear cooling spacePer manufacturer specificationsBehindAdditional space for cooling at rear in accordance with manufacturer specificationsFigure 28 - Static UPS area and height
    Equipment InstallationPackaged SubstationsBase allowance100 mmBelowConcrete base allowanceFigure 30 - Packaged substations area and height
    Equipment InstallationPackaged SubstationsCrawl access space790 mmAboveCrawl access space above unit for maintenanceFigure 30 - Packaged substations area and height
    Equipment InstallationUPS Battery RacksMaximum safe height2,000 mm maximumAbove floorFor safe access to battery rack, height should not exceed 2 mFigure 32 - UPS battery rooms area and height
    Equipment InstallationLV Switch Rooms (up to 750 kVA)Cable installation height1,000 mmAboveHeight allowance for cable installation for ratings up to 750 kVAFigure 34 - Switch rooms area and height
    Equipment InstallationLV Switch Rooms (≥1,000 kVA)Cable installation height1,500 mmAboveHeight allowance for cable installation for ratings 1,000 kVA and aboveFigure 34 - Switch rooms area and height
    Equipment InstallationLV Switch RoomsBase allowance100 mmBelowConcrete base allowanceFigure 34 - Switch rooms area and height
    Equipment InstallationTransformersBase allowance100 mmBelowConcrete base allowanceFigure 36 - Transformers area and height
    Equipment InstallationTransformersCable installation height1,000 mmAboveHeight allowance for cable installationFigure 36 - Transformers area and height
    Maintenance AccessSwitchgearOperating and maintenance gangways700 mm minimumAll sidesGangways should permit at least 90° opening of equipment doors or hinged panelsFigure 38 - Switchgear space for operating and maintenance (Based on BS 7671)
    SafetySwitchgearSafety clearance from live parts2,000 mm height, 2,500 mm overallAbove and around live partsFor placing electrical equipment out of reach per BS 7671 Regulation 417.3Figure 38 - Switchgear space for operating and maintenance (Based on BS 7671)
    Building ServicesCeiling Voids - StructuralStructural deflection50 mmAbove structural elementsAllowance for structural deflection plus toleranceFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesCeiling Voids - SprinklerSprinkler zone50 mm + 150 mmAbove other servicesClearance zone for sprinkler systemsFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesCeiling Voids - LightingLighting zone150 mmBelow ceilingZone allocation for lighting installationsFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesCeiling Voids - LuminairesLuminaire removal clearance1.5 times luminaire heightAround luminairesClearance to facilitate removal of lighting fittings and heat dissipationFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesCeiling VoidsCeiling deflection50 mmBelow ceilingAllowance for ceiling deflectionFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesFloor Voids - OfficeTypical office access150 mm minimumUnder raised floorMinimum access space under raised floors for typical officesFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesFloor Voids - Trading FloorTrading floor access300-500 mmUnder raised floorEnhanced access space for trading floorsFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesAccess PanelsMinimum panel size600 mm x 600 mm minimumMultiple locationsMinimum size for access panels throughout building servicesFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesTerminal UnitsMaintenance access500 mm minimumAround terminal unitsClear access to terminal units for maintenanceFigure 39 - Ceiling and floor voids in a generic office building
    Maintenance ReachStanding Maintenance WorkMaximum reach height2,100 mm maximumAbove floor levelMaximum height for safe standing maintenance accessFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachProne Maintenance WorkMinimum height for prone access450 mmHeight clearanceMinimum height required for prone maintenance positionFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachCrawl Maintenance WorkMinimum height for crawling900 mmHeight clearanceMinimum height required for crawling maintenance accessFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachStooping Maintenance WorkMinimum height for stooping900 mmHeight clearanceMinimum height required for stooping maintenance workFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachSquatting Maintenance WorkMinimum height for squatting690 mmHeight clearanceMinimum height required for squatting maintenance positionFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachKneeling Maintenance WorkMinimum height for kneeling1,100 mmHeight clearanceMinimum height required for kneeling maintenance workFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Access RoutesPassageway - Single PersonWidth550 mm minimum, 750 mm optimumWidthWidth requirement for single person passageFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Access RoutesLadderWidth380 mm minimum, 450 mm optimumWidthLadder width requirements for safe accessPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesLadderSide clearance600 mm minimumBetween side wallsClear space required around ladder between side wallsPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesInclined LadderWidth with handrails530-600 mmWidth including handrailsWidth including handrails for inclined laddersPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesStairs - Single PersonWidth600-750 mmWidthWidth for single person stair accessPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesStairs - Two PersonWidth1,100 mm minimumWidthWidth for two people on stairs simultaneouslyPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesRampWidth750 mm minimum, 1,100 mm optimumWidthRamp width requirements for safe accessPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesLadder RungsRung spacing and diameter180-406 mm spacing, 20-40 mm diameterVertical spacing and rung size300 mm optimum spacing, standard rung diameter rangePage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesStair Treads and RisersTread and riser dimensions240 mm optimum tread, 250 mm maximum riserStair geometryOptimum tread depth and maximum riser height for safetyPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    On This page

      3 responses

      1. Hey Jarek, just reading your latest post about clearance rules.

        Your 100% correct you won’t find a blanket 1,000 mm clearance rule written into UK legislation or BS 7671 as far as I’m aware.

        Exactly as you said, Legislation / ADB / HSG85 / CDM all talk about providing safe access, safe working space, and designing out maintenance risks, but none of them give a fixed measurement.

        My work is mainly in the water industry, and this is where the 1 m clearance does appear – but only in sector or client specifications, not in the regs. The water industry standard WIMES 3.02 calls for 1 m clearance around LV assemblies so you can open doors properly, withdraw ACBs for normal operation and maintenance, and provide safe escape in an emergency.

        Let me know if you find anything.

        Thanks,
        Dan

        1. Thanks, Dan — really appreciate you sharing the water-industry context. I’ve updated the post thanks to you.

      Leave a Reply

      Your email address will not be published. Required fields are marked *

      share this page