On this page:

    Electrical & Mechanical Equipment: Access & Maintenance (UK)

    “Electrical equipment shall be arranged to provide: 1. sufficient space for the initial installation and later replacement of individual items of electrical equipment; 2. accessibility for operation, inspection, testing, fault detection, maintenance and repair.”
    Reference: BS 7671:2018+A4:2026, Regulation 132.12

    “Except for a joint in cables where Section 526 allows such a joint to be inaccessible, every item of equipment shall be arranged so as to facilitate its operation, inspection and maintenance and access to each connection. Such facility shall not be significantly impaired by mounting equipment in an enclosure or a compartment.”
    Reference: BS 7671:2018+A4:2026, Regulation 513.1

    There is no universal 1 m rule in UK law or in BS 7671. The legal duty is Regulation 15 of the Electricity at Work Regulations 1989, and the dimensions are in BS 7671 Section 729, the manufacturer’s instructions and client specifications such as WIMES 3.02. This guide covers switchrooms, distribution board positions and plant space in buildings in England.

    Checklist

    • Classify the space: restricted access area (skilled or instructed persons only, signed, no access for unauthorised persons) or general access area. [BS 7671 Regulation 729.3]
    • Restricted access area: gangway 700 mm wide and 2,000 mm high, live parts 2,500 mm out of reach, doors opening outwards at least 700 mm wide and 2,000 mm high, gangways longer than 10 m accessible from both ends. [BS 7671 Section 729]
    • General access area: adequate working space, means of access and lighting for the work being done. [Electricity at Work Regulations 1989, Regulation 15]
    • Manufacturer’s instructions: apply the service envelope stated, where it exceeds 700 mm. [BS 7671 Regulation 510.3]
    • Client or sector specification: WIMES 3.02 requires a 1,000 mm gangway. Apply it where the project requires it.
    • Record the decision: the classification and the rules applied, in the design risk register. [CDM 2015, Regulation 9]

    1. What the law actually requires (baseline for every project)

    • EAWR Reg. 15: provide adequate working space, adequate means of access and adequate lighting at electrical equipment where work may give rise to danger. It is the legal basis for every layout and clearance decision. [Electricity at Work Regulations 1989, Regulation 15]
    • CDM 2015 (designer duty): design to eliminate, reduce or control foreseeable risks; provide enough information with the design so others can comply. (Use this to justify room sizing, door swing, heavy-item removal routes, etc.) [CDM 2015, Regulation 9]
    • HSG85: practical HSE guidance on safe working around electrical gear (planning, safe access/space, lighting). Use it to evidence your maintenance reasoning alongside EAWR. [HSE HSG85, Electricity at work: safe working practices, third edition 2013]
    • Fire service access overlay (ADB B5): coordinate plant room locations and external access with the vehicle access rules (e.g., a door every 60 m at most on accessible elevations; min 750 mm door width). [Approved Document B Volume 2, paragraph 15.3]
    • Electrical equipment of machines (BS EN 60204-1): this standard applies to the electrical equipment of machines, not to the building installation. For the control panels within its scope it states: “All controlgear shall be mounted so as to facilitate its operation and maintenance. Where a special tool is necessary to adjust, maintain, or remove a device, such a tool shall be supplied. Where access is required for regular maintenance or adjustment, the relevant devices shall be located between 0,4 m and 2,0 m above the servicing level. It is recommended that terminals be at least 0,2 m above the servicing level and be so placed that conductors and cables can be easily connected to them.” It also states: “It is recommended that electrical equipment mounted inside enclosures be designed and constructed in such a way as to permit modification of the wiring from the front of the enclosure. Where that is not practicable and control devices are connected from the rear of the enclosure, access doors or swing-out panels shall be provided.” [BS EN 60204-1:2018+A1:2025]

    2. When BS 7671 gives you actual numbers

    In restricted access areas (switchrooms, locked plant areas and roofs where access is restricted to skilled or instructed persons), BS 7671 Section 729 gives the minimum gangway dimensions and the conditions for operation and maintenance:

    • Gangway width: 700 mm minimum, measured with circuit-breakers and switch handles in the most onerous position, including isolation. [BS 7671:2018+A4:2026, Regulation 729.513.2.1]
    • Gangway height: 2,000 mm minimum to the barrier, enclosure or obstacle. [Regulation 729.513.2.1]
    • Live parts placed out of reach: 2,500 mm minimum. [Regulation 729.513.2.1 and Regulation 417.3]
    • Equipment doors and hinged panels: gangways shall permit at least a 90 degree opening. [Regulation 729.513.2]
    • Access from both ends: gangways longer than 10 m shall be accessible from both ends. Closed restricted access areas longer than 20 m shall be accessible by doors from both ends. For closed areas longer than 6 m, access from both ends is recommended. [Regulation 729.513.2.3]

    Where additional workspace is needed, for example for special switchgear and controlgear assemblies, larger dimensions may be required. [Regulation 729.513.2.1, Note]. The manufacturer’s instructions may require more than these minimums (see Manufacturer’s instructions below).

    Section through a restricted access area: 700 mm minimum gangway width to the wall and between enclosures, 2,000 mm height to the barrier or enclosure, 2,500 mm to live parts placed out of reach, circuit-breaker in the isolation position. Dimensions from BS 7671 Regulation 729.513.2.1. Project Design drawing.
    • Basic protection by barriers or enclosures (Figure 729.1): 700 mm gangway width, 2,000 mm height to the barrier or enclosure, 2,500 mm to live parts placed out of reach. [BS 7671:2018+A4:2026, Regulation 729.513.2.1]
    • Protective measure of obstacles (Figure 729.2): the same minimums, 700 mm gangway width, 2,000 mm height to the obstacle and 2,500 mm to live parts placed out of reach, and Section 417 applies. This measure is for installations controlled or supervised by skilled persons. [BS 7671:2018+A4:2026, Regulation 729.513.2.2]
    • Note: the HSE would not expect to see any new switchboard installed in the UK where there was potential access to live exposed busbars. [IET Guidance Note 7, 8th edition, 17.3.3]

    Corrected 23 September 2026: an earlier version of this section gave 900 mm, 1,100 mm and 1,300 mm gangway figures for exposed live parts. Those figures are not in BS 7671.

    Restricted and open access areas (who the room is for)

    • Restricted access areas shall be clearly and visibly marked by appropriate signs and shall not provide access to unauthorised persons. (This is the premise for applying the Section 729 dimensions to switchrooms and distribution board rooms.) [BS 7671:2018+A4:2026, Regulation 729.3]

    End wall clearance for long runs

    • For long line-ups, place equipment a minimum of 700 mm from all walls, or provide an access door on the wall against which the equipment is positioned, so that gangways longer than 10 m are accessible from both ends. Closed restricted access areas longer than 20 m shall have doors at both ends. [BS 7671:2018+A4:2026, Regulation 729.513.2.3 and Note 1]

    Isolation and emergency switching (applies to all panels and distribution boards)

    • Ensure suitable means are available for cutting off the supply and for isolation; “isolation” means secure disconnection and separation from every source of electrical energy. (Position, labelling and access to these devices must reflect the EAWR duty.) [Electricity at Work Regulations 1989, Regulation 12]

    Consumer units and distribution boards in general access spaces: where a board is not in a restricted access area (a riser cupboard serving common parts, for example), Regulation 15 of the Electricity at Work Regulations 1989 and the manufacturer’s instructions set the working space and the reach to the means of isolation. BS 7671 gives no working depth for these positions. Apply the depth the manufacturer states. [Electricity at Work Regulations 1989, Regulation 15; BS 7671 Regulation 510.3]

    In dwellings, Approved Document M gives the mounting height for equipment not intended for regular user interaction, such as meter cupboards and consumer units:

    “Reasonable provision should be made to ensure that the approach route to any communal facilities that serve the dwelling meets these provisions. Communal facilities include storage areas, such as those used for depositing refuse and recycling, but not plant rooms or other service areas unless occupants need regular access, for example for meter reading.
    Reference: Approved Document M Volume 1 (2015 edition incorporating 2016 amendments), paragraph 2.4

    Consumer units are mounted so that the switches are 1350-1450mm above floor level”
    Reference: Approved Document M Volume 1, paragraph 1.18

    3. Access during maintenance (doors/withdrawable gear)

    For easy evacuation, the doors of any equipment inside the location shall close in the direction of the evacuation route, and gangways shall permit at least a 90 degree opening of equipment doors or hinged panels. [BS 7671:2018+A4:2026, Annex A729 (normative), A729.1]

    • Case 1, circuit-breakers in the isolated position and all doors closed: minimum passing width 700 mm. [Figure A729.1]
    • Case 2, doors fixed open and circuit-breakers fully withdrawn: minimum 500 mm between the door edge or circuit-breaker edge and the opposite limit of the gangway. [Figure A729.2]
    Two plan views of a switchgear assembly: Case 1 with circuit-breakers isolated and doors closed, 700 mm minimum passing width; Case 2 with doors fixed open at 90 degrees and circuit-breakers completely extracted, 500 mm minimum. Dimensions from BS 7671 Annex A729. Project Design drawing.

    4. Length, exits and door geometry

    • Gangways longer than 10 m shall be accessible from both ends. Closed restricted access areas longer than 20 m shall be accessible by doors from both ends. For closed areas longer than 6 m, access from both ends is recommended. [BS 7671:2018+A4:2026, Regulation 729.513.2.3]
    • Doors giving access to gangways shall open outwards and shall be at least 700 mm wide and 2,000 mm high. [BS 7671:2018+A4:2026, Regulation 729.513.2.3]
    • Doors provided for closed restricted access areas shall allow easy evacuation by opening without the use of a key, tool or any other device not being part of the opening mechanism. [BS 7671:2018+A4:2026, Regulation 729.3]
    • Gangways shall permit at least a 90 degree opening of equipment doors or hinged panels. [BS 7671:2018+A4:2026, Regulation 729.513.2]
    Three plan views: gangway 10 m or less with one door; gangway longer than 10 m with equipment 700 mm from the end walls and one door; closed area longer than 20 m with doors at both ends. Dimensions from BS 7671 Regulation 729.513.2.3. Project Design drawing.

    5. Where “1 m clearance” comes from

    credit: Dan Oxford

    The Water Industry Mechanical and Electrical Specifications (WIMES) 3.02, Low Voltage Electrical Installations, extends the BS 7671 gangway width to 1,000 mm:

    “The minimum distance specified for the width of a maintenance gangway in Section 729 of BS 7671 is 700 mm, however, extending this to 1000 mm in this Specification is considered a reasonable measure to facilitate all foreseeable Assembly installation, operation and maintenance activities.”
    Reference: WIMES 3.02 Low Voltage Electrical Installations, clause 3.3.5, quoted from an extract of the specification supplied by Dan Oxford. Check the clause against the WIMES issue current on your project.

    WIMES 3.02 clause 3.3.5 specification extract

    Manufacturer’s instructions

    Selection and erection shall take account of the manufacturer’s instructions. Where the manufacturer’s instructions or the project specification require a working depth of 1,000 mm or more in front of the assembly, that dimension is the project requirement, above the 700 mm minimum in BS 7671. Example: Schneider Electric FAQ FA32222. [BS 7671 Regulation 510.3]

    6. Firefighting access (layout coordination)

    Requirement B5 requires reasonable facilities to assist fire fighters and reasonable provision within the site for fire appliance access. Use it to coordinate plant room positions, switchgear access routes and external yard clearances. [Building Regulations 2010, Schedule 1, Requirement B5; Approved Document B Volume 2, Section 15]

    • Buildings up to 2,000 m² with the top storey at most 11 m above ground: vehicle access for a pump appliance to 15% of the perimeter, or to within 45 m of every point of the footprint, whichever is less onerous. [Approved Document B Volume 2, paragraph 15.1]
    • Larger buildings: vehicle access to the percentage of the perimeter in Table 15.1. [paragraph 15.2]
    • Every elevation with vehicle access: a door at least 750 mm wide into the building, with no more than 60 m between doors or between a door and the end of the elevation. [paragraph 15.3]

    7. Practical layout rules

    Step 1: Classify the space

    • Restricted access areas (switchrooms, risers, plant decks; skilled or instructed persons only): BS 7671 Section 729 applies to the gangways and working space, together with the manufacturer’s instructions.
    • General access areas: Regulation 15 of the Electricity at Work Regulations 1989 (adequate working space, means of access and lighting) and HSG85 apply. [Electricity at Work Regulations 1989, Regulation 15; HSE HSG85]

    Step 2: Apply Part M

    • Dwellings (Volume 1): switches and sockets with their centre line 450 mm to 1,200 mm above floor level; consumer unit switches 1,350 mm to 1,450 mm above floor level (Diagram 1.5). [Approved Document M Volume 1, paragraph 1.18]
    • Buildings other than dwellings (Volume 2): the accessibility requirements apply to the spaces people use. Requirement M1 does not apply to any part of a building that is used solely to enable the building or any service or fitting in the building to be inspected, repaired or maintained, so plant rooms and risers are not Part M spaces. Regulation 15, HSG85, BS 7671 and the manufacturer’s instructions apply there. [Building Regulations 2010, Schedule 1, Part M, limits on application]

    Step 3: Apply the manufacturer’s and the client’s requirements

    • Where the manufacturer’s instructions state more than 700 mm, or a service envelope for withdrawing air circuit-breakers, that dimension applies. [BS 7671 Regulation 510.3]
    • Where the client or the sector has a specification, it is a project requirement. WIMES 3.02 in the water industry requires a 1,000 mm gangway.

    Step 4: Egress and doors during maintenance

    • Keep the passing width with equipment doors and panels open to 90 degrees and circuit-breakers withdrawn: 700 mm with doors closed and circuit-breakers isolated, 500 mm with doors fixed open and circuit-breakers fully withdrawn. [BS 7671 Annex A729]
    • Gangways longer than 10 m: access from both ends. Closed restricted access areas longer than 20 m: doors at both ends. [BS 7671 Regulation 729.513.2.3]
    • Fire and rescue service access: where the plant room sits on an elevation with vehicle access, check the external door spacing and widths against Approved Document B Volume 2, Section 15.
    • Where WIMES 3.02 applies: show the 1,000 mm clearance in front of the LV assemblies on the general arrangement drawings and elevations, keep it clear of other services and cable ladders, and state it in the room data sheet and the specification. The clearance allows full door opening, a safe operator stance, withdrawal of air circuit-breakers and draw-out units, and a clear escape route in front of the assembly. WIMES is a client specification, not legislation. (Dan Oxford, comment on this post, 29 August 2025.)

    Step 5: Record the decision

    • State in the design risk register and the specification: the room classification, the rules applied (Electricity at Work Regulations, HSG85, BS 7671, Part M, the manufacturer’s instructions, WIMES), how evacuation is maintained during maintenance, and the removal routes for heavy components. [CDM 2015, Regulation 9]

    Switchroom and plant space layouts are part of PD’s electrical design services.

    8. Means of escape for fire safety

    Part B of the Building Regulations (England) sets the fire safety requirements for building work. Approved Document B gives the guidance in two volumes: Volume 1 for dwellings and Volume 2 for buildings other than dwellings.

    The three tables below are Tables 2.3, 2.2 and 2.1 of Approved Document B Volume 2 (2019 edition incorporating 2020 and 2022 amendments). They apply to buildings other than dwellings. Other approaches may be valid: check with the project’s fire safety consultant and building control body.

    Table 2.3 Widths of escape routes and exits

    Maximum number of peopleMinimum width
    60750 mm
    110850 mm
    2201,050 mm
    More than 2205 mm per person

    Table 2.2 Minimum number of escape routes and exits from a room, tier or storey

    Minimum number of peopleMinimum number of escape routes
    601
    6002
    more than 6003

    Table 2.1 Limitations on travel distance

    Type of buildingMaximum travel distance for escape available in one directionMaximum travel distance for escape available in at least two directions
    Residential (institutional)9 m18 m
    Residential (other) in bedrooms [i]9 m18 m
    Residential (other) in bedroom corridors [ii]9 m35 m
    Residential (other) elsewhere18 m35 m
    Offices18 m45 m
    Shop and commercial premises18 m45 m
    Assembly and recreation buildings primarily for disabled people9 m18 m
    Assembly and recreation buildings with fixed seating in rows15 m32 m
    Assembly and recreation buildings (elsewhere)18 m45 m
    Industrial buildings, storage and other non-residential (normal hazard) [iii]25 m45 m
    Industrial buildings, storage and other non-residential (higher hazard) [iii]12 m25 m
    Place of special fire hazard [iv]9 m [v]18 m [v]
    Plant room or rooftop plant (distance within the room)9 m35 m
    Plant room or rooftop plant with escape route not in open air (overall travel distance)18 m45 m
    Plant room or rooftop plant with escape route in open air (overall travel distance)60 m100 m

    Notes to Table 2.1:
    [i] Maximum part of travel distance within the room. This limit applies within the bedroom and any associated dressing room, bathroom or sitting room, etc. The distance is measured to the door to the protected corridor that serves the room or suite.
    [ii] Maximum part of travel distance applying from that point along the bedroom corridor to a storey exit.
    [iii] The appropriate travel distance depends on the level of fire hazard associated with the processes and materials being used. For the definition of higher hazard, refer to Approved Document B Volume 2.
    [iv] This is defined as a room such as an oil-filled transformer room, switch gear room, boiler room, storage space for fuel or other highly flammable substances or a room that houses a fixed internal combustion engine.
    [v] Maximum part of travel distance within the room/area. Travel distance outside the room/area should comply with the limits for the purpose group of the building or part.

    General note to Table 2.1:
    If the internal layout of partitions, fittings, etc. is not known, direct distances, rather than travel distances, should be assessed. The direct distance should be assumed to be two-thirds of the actual travel distance.

    Notes to Table 2.3:
    Widths less than 1,050 mm should not be interpolated. The 5 mm per person figure does not apply to an opening serving fewer than 220 people. Widths may need to be increased to meet the guidance in Approved Document M.

    9. Human factors & reach distances

    The figures below are from BSRIA BG 84/2024, Figure 40 (space requirements and reach distances for installation and maintenance tasks). BSRIA bases the figure on BS 8313 as amended in BG 55.

    Passageway:
    Height: 2,100 mm minimum
    Width: 550 mm minimum, 750 mm optimum

    Maintenance reach levels:
    Standing: 900 mm to 1.5 m
    Kneeling: 600 mm
    Sitting: 300 mm

    Working postures (length by height):
    Prone: 2.5 m by 450 mm
    Crawl: 1.5 m by 790 mm
    Squat: 690 mm by 1.2 m
    Kneel: 1.1 m by 1.4 m
    Stoop: 900 mm by 900 mm

    Access routes:
    Stairs: 600 mm to 750 mm for one person, 1.1 m minimum for two people
    Ramps: 750 mm minimum, 1.1 m optimum, incline not to exceed 20 degrees
    Ladders: 380 mm minimum, 450 mm optimum, 600 mm minimum between side walls

    Source: BSRIA BG 84/2024, general building services section, Figure 40 and the access route figure that follows it.

    Passageway 2,100 mm minimum high, 550 mm minimum and 750 mm optimum wide, with a standing figure; maintenance reach levels of 1.5 m, 1.2 m and 900 mm standing, 600 mm kneeling and 300 mm sitting. Dimensions from BSRIA BG 84/2024 Figure 40. Project Design drawing.

    Image: BSRIA BG 84/2024, Figure 40 (based on BS 8313 and amended in BG 55).

    10. BG 84/2024 space planning allowances (early design stage)

    During concept design and feasibility studies, use the BSRIA space and weight allowances to size plant rooms, coordinate structural loads and check access routes before the equipment is selected. The allowances in BSRIA BG 84/2024 give approximate space envelopes for common building services equipment, including maintenance access, concrete bases, cable and pipe clearances and heat dissipation zones.

    Uses:

    • Plant room sizing during architectural coordination
    • Structural loading estimates for slab design
    • Access route planning for equipment delivery and replacement
    • Space budgeting across the mechanical and electrical disciplines

    Note: these are preliminary allowances. Confirm them against the manufacturer’s datasheets, the detailed calculations and the current standards at detailed design.

    The table below lists space allowances from BSRIA BG 84/2024, with the figure each one comes from. They are rules of thumb for early design, not requirements of any British Standard.

    CategoryEquipmentAllowance typeDimensionLocationNotesReference
    Equipment InstallationBiomass BoilersBase allowance150 mmBelowConcrete base allowanceFigure 1 - Biomass boiler plant room area and height
    Equipment InstallationAir Cooled CondensersBase and anti-vibration mounts300 mmBelowBase and anti-vibration mounts allowanceFigure 4 - Air cooled condensers area and height
    Equipment InstallationAir Cooled CondensersHeat dissipation clearanceClear height requiredAboveClear height above units must be provided for vertical air discharge to allow heat to dissipateFigure 4 - Air cooled condensers area and height
    Equipment InstallationAir Handling UnitsBase and condensate trap200 mmBelowBase and condensate trap allowanceFigure 6 - Air handling units area and height
    Equipment InstallationAir Handling UnitsCrawl space above unit790 mmAboveCrawl space above each unit for maintenance accessFigure 6 - Air handling units area and height
    Equipment InstallationGas Fired BoilersBase allowance150 mmBelowConcrete base allowanceFigure 8 - Gas fired boiler plant room area and height
    Equipment InstallationHorizontal CalorifiersBase allowance100 mmBelowConcrete base allowanceFigure 10 - Horizontal calorifiers area and height
    Equipment InstallationHorizontal CalorifiersPipework clearance1,000 mmAboveHeight allowance for pipeworkFigure 10 - Horizontal calorifiers area and height
    Equipment InstallationVertical CalorifiersBase allowance100 mmBelowConcrete base allowanceFigure 12 - Vertical calorifiers area and height
    Equipment InstallationVertical CalorifiersPipework clearance1,000 mmAboveHeight allowance for pipeworkFigure 12 - Vertical calorifiers area and height
    Equipment InstallationAir Cooled ChillersBase and anti-vibration mounts300 mmBelowBase and anti-vibration mounts allowanceFigure 14 - Air cooled chillers area and height
    Equipment InstallationAir Cooled ChillersHeat dissipation clearanceClear height requiredAboveClear height above units must be provided for vertical air discharge to allow heat to dissipateFigure 14 - Air cooled chillers area and height
    Equipment InstallationWater Cooled ChillersBase and anti-vibration mounts300 mmBelowConcrete base and anti-vibration mounts allowanceFigure 16 - Water cooled chillers area and height
    Equipment InstallationForced Draught Cooling TowersBase allowance200 mmBelowBase allowance for foundationFigure 18 - Forced draught cooling tower area and height
    Equipment InstallationForced Draught Cooling TowersHeat dissipation clearanceClear height requiredAboveClear height above units for vertical air discharge to allow heat to dissipateFigure 18 - Forced draught cooling tower area and height
    Equipment InstallationInduced Draught Cooling TowersBase allowance200 mmBelowBase allowance for foundationFigure 20 - Induced draught cooling tower area and height
    Equipment InstallationInduced Draught Cooling TowersHeat dissipation clearanceClear height requiredAboveClear height above units for vertical air discharge to allow heat to dissipateFigure 20 - Induced draught cooling tower area and height
    Equipment InstallationCold Water Storage TanksBase allowance150 mmBelowConcrete base allowanceFigure 22 - Cold water storage area and height
    Equipment InstallationCold Water Storage TanksFreeboard height500 mmAbove water levelFreeboard height allowance above maximum water levelFigure 22 - Cold water storage area and height
    Equipment InstallationCold Water Storage TanksCrawl space above tank790 mmAboveCrawl space above tank for maintenance accessFigure 22 - Cold water storage area and height
    Equipment InstallationCold Water Storage Tanks (External Flange)Additional height for external flange500 mmAboveAdditional height allowance if externally flanged tank is usedFigure 22 - Cold water storage area and height
    Equipment InstallationDiesel GeneratorsBase and anti-vibration mounts300 mmBelowConcrete base and anti-vibration mounts allowanceFigure 24 - Diesel generators area and height
    Equipment InstallationDiesel GeneratorsCrawl space above unit790 mmAboveCrawl space above unit for maintenance accessFigure 24 - Diesel generators area and height
    Equipment InstallationHybrid Rotary UPSBase allowance100 mmBelowConcrete base allowanceFigure 26 - Hybrid rotary UPS area and height
    Equipment InstallationHybrid Rotary UPSCable installation height1,000 mmAboveHeight allowance for cable installationFigure 26 - Hybrid rotary UPS area and height
    Equipment InstallationStatic UPSCable installation spaceAdditional space requiredTop and bottomAdditional space should be provided at top and bottom for cable installationFigure 28 - Static UPS area and height
    Equipment InstallationStatic UPS (≥400 kVA)Cooling clearance400 mmAboveAdditional clearance at top for cooling purposes for UPS rated 400 kVA or aboveFigure 28 - Static UPS area and height
    Equipment InstallationStatic UPSRear cooling spacePer manufacturer specificationsBehindAdditional space for cooling at rear in accordance with manufacturer specificationsFigure 28 - Static UPS area and height
    Equipment InstallationPackaged SubstationsBase allowance100 mmBelowConcrete base allowanceFigure 30 - Packaged substations area and height
    Equipment InstallationPackaged SubstationsCrawl access space790 mmAboveCrawl access space above unit for maintenanceFigure 30 - Packaged substations area and height
    Equipment InstallationUPS Battery RacksMaximum safe height2,000 mm maximumAbove floorFor safe access to battery rack, height should not exceed 2 mFigure 32 - UPS battery rooms area and height
    Equipment InstallationLV Switch Rooms (up to 750 kVA)Cable installation height1,000 mmAboveHeight allowance for cable installation for ratings up to 750 kVAFigure 34 - Switch rooms area and height
    Equipment InstallationLV Switch Rooms (≥1,000 kVA)Cable installation height1,500 mmAboveHeight allowance for cable installation for ratings 1,000 kVA and aboveFigure 34 - Switch rooms area and height
    Equipment InstallationLV Switch RoomsBase allowance100 mmBelowConcrete base allowanceFigure 34 - Switch rooms area and height
    Equipment InstallationTransformersBase allowance100 mmBelowConcrete base allowanceFigure 36 - Transformers area and height
    Equipment InstallationTransformersCable installation height1,000 mmAboveHeight allowance for cable installationFigure 36 - Transformers area and height
    Maintenance AccessSwitchgearOperating and maintenance gangways700 mm minimumAll sidesGangways should permit at least 90° opening of equipment doors or hinged panelsFigure 38 - Switchgear space for operating and maintenance (Based on BS 7671)
    SafetySwitchgearSafety clearance from live parts2,000 mm height, 2,500 mm overallAbove and around live partsFor placing electrical equipment out of reach per BS 7671 Regulation 417.3Figure 38 - Switchgear space for operating and maintenance (Based on BS 7671)
    Building ServicesCeiling Voids - StructuralStructural deflection50 mmAbove structural elementsAllowance for structural deflection plus toleranceFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesCeiling Voids - SprinklerSprinkler zone50 mm + 150 mmAbove other servicesClearance zone for sprinkler systemsFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesCeiling Voids - LightingLighting zone150 mmBelow ceilingZone allocation for lighting installationsFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesCeiling Voids - LuminairesLuminaire removal clearance1.5 times luminaire heightAround luminairesClearance to facilitate removal of lighting fittings and heat dissipationFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesCeiling VoidsCeiling deflection50 mmBelow ceilingAllowance for ceiling deflectionFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesFloor Voids - OfficeTypical office access150 mm minimumUnder raised floorMinimum access space under raised floors for typical officesFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesFloor Voids - Trading FloorTrading floor access300-500 mmUnder raised floorEnhanced access space for trading floorsFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesAccess PanelsMinimum panel size600 mm x 600 mm minimumMultiple locationsMinimum size for access panels throughout building servicesFigure 39 - Ceiling and floor voids in a generic office building
    Building ServicesTerminal UnitsMaintenance access500 mm minimumAround terminal unitsClear access to terminal units for maintenanceFigure 39 - Ceiling and floor voids in a generic office building
    Maintenance ReachStanding Maintenance WorkMaximum reach height2,100 mm maximumAbove floor levelMaximum height for safe standing maintenance accessFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachProne Maintenance WorkMinimum height for prone access450 mmHeight clearanceMinimum height required for prone maintenance positionFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachCrawl Maintenance WorkMinimum height for crawling900 mmHeight clearanceMinimum height required for crawling maintenance accessFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachStooping Maintenance WorkMinimum height for stooping900 mmHeight clearanceMinimum height required for stooping maintenance workFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachSquatting Maintenance WorkMinimum height for squatting690 mmHeight clearanceMinimum height required for squatting maintenance positionFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Maintenance ReachKneeling Maintenance WorkMinimum height for kneeling1,100 mmHeight clearanceMinimum height required for kneeling maintenance workFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Access RoutesPassageway - Single PersonWidth550 mm minimum, 750 mm optimumWidthWidth requirement for single person passageFigure 40 - Space requirements and reach distances (Based on BS 8313 amended in BG 55)
    Access RoutesLadderWidth380 mm minimum, 450 mm optimumWidthLadder width requirements for safe accessPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesLadderSide clearance600 mm minimumBetween side wallsClear space required around ladder between side wallsPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesInclined LadderWidth with handrails530-600 mmWidth including handrailsWidth including handrails for inclined laddersPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesStairs - Single PersonWidth600-750 mmWidthWidth for single person stair accessPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesStairs - Two PersonWidth1,100 mm minimumWidthWidth for two people on stairs simultaneouslyPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesRampWidth750 mm minimum, 1,100 mm optimumWidthRamp width requirements for safe accessPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesLadder RungsRung spacing and diameter180-406 mm spacing, 20-40 mm diameterVertical spacing and rung size300 mm optimum spacing, standard rung diameter rangePage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    Access RoutesStair Treads and RisersTread and riser dimensions240 mm optimum tread, 250 mm maximum riserStair geometryOptimum tread depth and maximum riser height for safetyPage 48 - Access route clearances (Based on BS 8313 amended in BG 55)
    On This page

      2 responses

      1. Hey Jarek, just reading your latest post about clearance rules.

        Your 100% correct you won’t find a blanket 1,000 mm clearance rule written into UK legislation or BS 7671 as far as I’m aware.

        Exactly as you said, Legislation / ADB / HSG85 / CDM all talk about providing safe access, safe working space, and designing out maintenance risks, but none of them give a fixed measurement.

        My work is mainly in the water industry, and this is where the 1 m clearance does appear – but only in sector or client specifications, not in the regs. The water industry standard WIMES 3.02 calls for 1 m clearance around LV assemblies so you can open doors properly, withdraw ACBs for normal operation and maintenance, and provide safe escape in an emergency.

        Let me know if you find anything.

        Thanks,
        Dan

      Leave a Reply

      Your email address will not be published. Required fields are marked *

      share this page