On this page:
    STANDARDS & DESIGN · CONTAINMENT

    Cable Ladder vs Perforated Cable Tray: Selection Guide

    On perforated cable tray and on cable ladder a circuit has the same tabulated current-carrying capacity but a different grouping factor. The duty (medium duty tray, heavy duty tray or ladder) is selected by comparing the load with the safe working load (SWL) of the particular containment at the support span. This guide sets out the eight decisions in order, to BS 7671:2018+A4:2026, BS EN 61537:2007 and BS 8519:2020, and refers to the guide How to size cable tray for the width calculation, fault restraint and drop rod sizing.

    Checklist

    References to BS 7671 in this guide are to BS 7671:2018+A4:2026.

    DecideWhat it setsReference
    Reference methodE or F on perforated tray and on ladder, so the same tabulated capacity; C on unperforated trayBS 7671 Table 4A2
    Grouping factorSeparate rows for tray and ladder; in Table 4C1 the ladder factor is higher from 4 circuitsBS 7671 Tables 4C1, 4C4, 4C5
    Cable type and fixingNo non-sheathed cables; cleats for single-core cablesBS 7671 Table 4A1, Regulation 521.5.201; IET On-Site Guide Table D1
    DutyMedium duty tray, heavy duty tray or ladder, from the load against the declared SWL at the spanBS EN 61537:2007, 10.1
    Width and self-weightThe weight on the supportsBS 8519:2020, Annex E
    FireSteel support; fire-rated SWL on a BS 8519 routeBS 7671 Regulation 521.10.202
    SegregationBand I and Band II separation; distance to data cablingBS 7671 Regulation 528.1; BS EN 50174-2:2018 Tables 8 and 9
    Material and finishSuitability for the external influencesBS 7671 Section 522

    1.0 Reference method

    Select the Installation Method in BS 7671 Table 4A2 for the support used.

    Table 1 Installation methods, BS 7671 Table 4A2.

    Installation MethodCablesReference Method
    30On unperforated trayC, with item 2 of Table 4C1
    31On perforated trayE or F
    32On brackets, or on wire mesh tray (cable basket)E or F
    33Spaced more than 0.3 times the cable diameter from a wallE, F or G
    34On a ladderE or F

    Reference Method E applies to multicore cables and F to single-core cables (titles of BS 7671 Tables 4C4 and 4C5).

    Cable tray systems: A perforated cable tray has a regular pattern of holes that occupy at least 30 % of the area of the base of the tray. The current-carrying capacity for cables attached to perforated cable trays should be taken as Reference Method E or F. The current-carrying capacity for cables attached to unperforated cable trays (no holes or holes that occupy less than 30 % of the area of the base of the tray) is to be taken as Reference Method C.
    BS 7671:2018+A4:2026, Appendix 4, 7.2.
    Cable ladder system: This is a construction which offers a minimum of impedance to the air flow around the cables, i.e. supporting metalwork under the cables occupies less than 10 % of the plan area. The current-carrying capacity for cables on ladder systems should be taken as Reference Method E or F.
    BS 7671:2018+A4:2026, Appendix 4, 7.2.

    The tabulated current-carrying capacity of one circuit is therefore the same on perforated tray and on ladder. For example, a three-core 25 mm² 70 °C thermoplastic SWA copper cable has a tabulated current-carrying capacity of 110 A on either (BS 7671 Table 4D4A, column 5).

    2.0 Grouping (Cg)

    Select the grouping factor from the row for the containment used, item 3 for perforated tray or item 4 for ladder.

    Table 2 One tray or ladder, single layer of multicore cables touching, Reference Method E, BS 7671 Table 4C1.

    CircuitsItem 3, perforated trayItem 4, ladder or cleats
    20.880.87
    30.820.82
    40.770.80
    50.750.80
    60.730.79
    70.730.79
    8 to 200.720.78

    For unperforated tray (Method 30), use item 2, single layer on a wall or floor, with Reference Method C. Item 2 is 0.72 at 6 circuits.

    Worked example.

    For six circuits touching, each tabulated at 110 A, Iz = 110 × 0.73 = 80.3 A on perforated tray and Iz = 110 × 0.79 = 86.9 A on ladder.

    Where horizontal clearances between adjacent cables exceed twice their overall diameter, no rating factor need be applied.
    BS 7671:2018+A4:2026, Table 4C1, Note 2.

    More than one tray, or cables spaced. BS 7671 Table 4C4 (multicore) and Table 4C5 (single-core circuits) give separate rows for perforated cable tray systems (Method 31) and for cable ladder systems, cleats, wire mesh tray, etc. (Methods 32 to 34). Use the ladder row for cable basket.

    Table 3 Examples from BS 7671 Tables 4C4 and 4C5.

    ArrangementPerforated trayLadder
    4C4, one tray, cables spaced, 6 cables0.911.00
    4C4, two trays, touching, 6 cables0.730.76
    4C4, two trays, touching, 9 cables0.680.73
    4C5, one tray, three three-phase circuits in horizontal formation0.870.96

    The factors of Tables 4C4 and 4C5 apply to single layer groups, not to cables in more than one layer touching each other (Note 2).

    Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable trays and wall. For closer spacing the factors should be reduced.
    BS 7671:2018+A4:2026, Tables 4C4 and 4C5, Note 3.

    3.0 Cable type and fixing

    Multicore cables. Fault-rated cleats are not required for multicore cables on a horizontal tray or ladder, as the electromechanical forces act between the cores and are contained within the cable (IET Guide to Cables and Cable Management, Section 8.5).

    Single-core cables. BS 7671 Regulation 521.5.201 states: “Every conductor or cable shall have adequate strength and be so installed as to withstand the electromechanical forces that may be caused by any current, including fault current, it may have to carry in service.” Restrain single-core cables with cleats selected against the short-circuit force calculated to BS EN 61914.

    Single-core cables armoured with steel wire or steel tape shall not be used for an AC circuit.
    BS 7671:2018+A4:2026, Regulation 521.5.2.

    Non-sheathed cables. BS 7671 Table 4A1 does not permit non-sheathed cables on cable ladder, cable tray or cable brackets, and Regulation 521.10.1 requires them to be enclosed in conduit, ducting or trunking. Non-sheathed protective conductors and protective bonding conductors need not be laid in conduits or ducts (Table 4A1, footnote).

    unsheathed, single insulated power cables should not be installed on cable ladder and cable tray.
    BEAMA, Best Practice Guide to Cable Ladder and Cable Tray Systems (November 2012), 2.10.1.

    Fixing spacing. Table D1 limits the spacing of fixings by the diameter and construction of the cable, on tray and on ladder alike.

    Table 4 Maximum spacing of fixings, horizontal runs (mm), IET On-Site Guide, Appendix D, Table D1.

    Overall diameter d (mm)Non-armouredArmoured
    d ≤ 9250not tabulated
    9 < d ≤ 15300350
    15 < d ≤ 20350400
    20 < d ≤ 40400450

    Above 40 mm the manufacturer’s recommendation applies. On a ladder a cable can be fixed only at a rung; on a perforated tray it can be fixed at any point. Check that the rung spacing in the ladder manufacturer’s data is within the Table D1 spacing for the smallest cable on the run.

    Note. The rung spacing check is PD’s interpretation of Table D1, not a requirement of BS 7671 or of the IET On-Site Guide.

    4.0 Duty and safe working load

    The choice between medium duty tray, heavy duty tray and cable ladder (medium or heavy duty) depends on the load against the SWL of the particular containment at the support span, not on the cable type alone. For each run:

    1. Add the weight of every cable, in kg/m, from the cable manufacturers’ data.
    2. Add the spare capacity allowance for future cables (see the Good practice line below).
    3. Compare the total with the SWL the manufacturer declares for the particular product, duty and width at the support span.
    4. Where the load is above the SWL, reduce the support span. Where a shorter span does not pass, select a heavier duty: heavy duty tray or ladder in place of medium duty tray, or heavy duty ladder in place of medium duty ladder. Where no span or duty passes, move cables to another run.

    The manufacturer declares the SWL in N/m (BS EN 61537:2007, 10.1). A load of 1 kg/m corresponds to 9.81 N/m.

    Good practice. BEAMA 3.4.1 describes an allowance for approximately 25% more cables as good design practice.

    On a BS 8519 route, Annex E recommends a spare capacity in the region of 20% to 30%, to be confirmed in the project requirements.

    For the declared application, the manufacturer or responsible vendor shall declare the SWL to be tested in N/m for each type of cable tray length or cable ladder length at specified distances, preferably in spans of 0,5 m increments, between the support devices
    BS EN 61537:2007, 10.1.

    BS EN 61537 defines no load class for the designer to specify. For a given product the SWL is lower at a longer span, so the same cables can pass on medium duty tray at a short span and need heavy duty tray or ladder at a longer one.

    Worked example.

    Six single-core 300 mm² AWA cables weigh 3.938 kg/m each (manufacturer’s data, as in the guide How to size cable tray). With a 25% spare capacity allowance the load is 6 × 3.938 × 1.25 = 29.5 kg/m, which is 290 N/m. Where the SWL the manufacturer declares for the medium duty tray at the support span is below 290 N/m, reduce the span or select heavy duty tray or ladder.

    The load on the supports and drop rods also includes every other service on the bracket (BS 8519:2020, Annex E, Note 3). On a BS 8519 fire-rated route, use the manufacturer’s fire-rated SWL at the fire survival time, not the ambient SWL.

    PD Tray. You can use PD Tray to check the load of each run of medium or heavy duty tray or medium or heavy duty ladder. The load check is indicative. It is made against a representative SWL for the duty chosen, or against the manufacturer’s SWL where you enter it (BS EN 61537). Where a run fails against the representative SWL, the result states the support spacing or the heavier duty that passes when the run is recalculated, or that cables are to be moved to another run. The load check is not made in the free version.

    5.0 Width and self-weight

    Include the self-weight of the containment at the width selected in the load on the supports and drop rods (BS 8519:2020, Annex E, Formula E.1).

    Table 5 Self-weight (kg/m), medium duty: Legrand Swifts MRF return flange tray and Unitrunk Speedway SW4 ladder.

    Width (mm)150300450600750900
    Tray1.303.075.507.2011.2313.23
    Ladder4.645.185.726.267.718.43

    In these two ranges the ladder is the heavier section up to 450 mm wide and the lighter from 600 mm. The catalogues list tray from 50 mm wide and ladder from 150 mm. These are two makers’ ranges, not a rule; check the product specified.

    Reference: Legrand Swifts and Unitrunk Speedway catalogue data.

    6.0 Fire

    Wiring systems shall be supported such that they will not be liable to premature collapse in the event of a fire.
    BS 7671:2018+A4:2026, Regulation 521.10.202.

    The regulation applies equally to tray and ladder. Cables in or on steel cable containment systems are deemed to meet the requirements of the regulation (Note 2). The regulation precludes non-metallic cable clips or cable ties as the sole means of support where cables are clipped direct to exposed surfaces or suspended under cable tray (Note 3). The regulation is not intended to maintain circuit integrity for life safety or firefighting applications (Note 5).

    BS 8519:2020 applies to fire-resistant power and control cable systems for life safety and firefighting. It gives no recommendations for installations covered by BS 5839-1, BS 5839-8, BS 5839-9 and BS 5266-1 (clause 1). Size the support system for the fire survival time, with drop rods to Annex E, Table E.2.

    7.0 Segregation and separation from data cabling

    Regulation 528.1 states no separation distance. It gives six methods, (a) to (f), for Band I and Band II circuits in one wiring system; method (d) is “the cables are installed on a cable tray system where physical separation is provided by a partition”.

    Cable ladder and cable tray systems on their own are passive in respect of electromagnetic influences.
    BEAMA, Best Practice Guide, 2.10.3.

    BS EN 50174-2:2018, Table 8 gives the minimum separation S between power cables and information technology cables by the screening of the containment, for the segregation classification of the information technology cable in Table 7. The minimum separation A is S multiplied by the power cabling factor P of Table 9 (6.2.1).

    Table 6 Minimum separation S, segregation classification b, BS EN 50174-2:2018, Table 8.

    No electromagnetic barrierOpen metallicPerforated metallicSolid metallic
    100 mm75 mm50 mm0 mm

    Footnote a states that open metallic containment is equivalent to a welded mesh steel basket of 50 mm × 100 mm mesh, and that steel tray (trunking without cover) of less than 1.0 mm wall thickness and/or more than 20% equally distributed perforated area achieves the same screening performance. Footnote b states that perforated metallic containment is equivalent to steel tray (trunking without cover) of at least 1.0 mm wall thickness and no more than 20% equally distributed perforated area. Footnote c requires the upper surface of the cables in perforated metallic containment to be at least 10 mm below the top of the containment.

    A perforated tray to BS 7671 Appendix 4, 7.2 has holes over at least 30% of its base, so the open metallic column applies to it. This is PD’s interpretation of footnote a, not a statement of the standard. Table 8 has no column for cable ladder; take the column from the wall thickness and perforated area of the containment.

    Fire alarm and emergency lighting. BS 5839-1:2025, clause 35.5 recommends that fire alarm cables should not be installed in the same conduit as other services and that, in common trunking, a compartment should be reserved solely for them. The clause applies to conduit and trunking, not to tray, ladder or basket. For central power supply systems in common containment, BS 5266-1:2025, clause 8.2.6 specifies a partition of the same base material, without perforation and as high as the sides.

    8.0 Material and finish

    Select the material and finish for the external influences of the route. The selection is the same for tray and ladder. Where hot dip galvanised ladder or tray is cut or drilled on site, the finish must be repaired to BS EN ISO 1461, usually with a zinc rich paint.

    Reference: BS 7671:2018+A4:2026, Section 522; BEAMA, Best Practice Guide, 2.9.2, 3.1, 3.2.

    9.0 Before you issue

    CheckConfirm
    Reference methodInstallation Method 30 to 34 for the support used, with its Reference Method
    GroupingThe tray or ladder row, with the vertical spacing between trays checked
    Cable typeNo non-sheathed cables; single-core cables cleated to the calculated force
    FixingFixing and rung spacing within Table D1 for the smallest cable
    DutyLoad with spare within the declared SWL at the span
    SupportsSelf-weight and other services included in the drop rod load
    FireSteel containment; fire-rated SWL on a BS 8519 route
    SegregationA Regulation 528.1 method; separation A = S (Table 8) × P (Table 9)
    FinishSuited to the external influences; cut galvanising repaired

    PD Tray

    You can use PD Tray to size each run of tray, ladder or basket, and the result states the BS 7671 table and row used for the containment chosen. The load check (the load of each run against an indicative safe working load, the load on each bracket and the drop rod size) comes with the Engineering Toolkit.

    10.0 References

    • BS 7671:2018+A4:2026, Requirements for Electrical Installations.
    • BS EN 61537:2007, cable tray systems and cable ladder systems.
    • BS 8519:2020, fire-resistant power and control cable systems.
    • BS EN 50174-2:2018, information technology cabling installation.
    • BS 5839-1:2025 and BS 5266-1:2025.
    • BS EN 61914, cable cleats; BS EN ISO 1461, hot dip galvanised coatings.
    • IET On-Site Guide; IET Guide to Cables and Cable Management.
    • BEAMA, Best Practice Guide to Cable Ladder and Cable Tray Systems (November 2012).

    Worked figures are illustrative.

    On This page

      Leave a Reply

      Your email address will not be published. Required fields are marked *

      share this page